beautypg.com

Warranty, Troubleshooting – Greenheck Vari-Green Control - Constant Pressure Indoor (474766) User Manual

Page 8

background image

8

AMCA Publication 410-96, Safety Practices for Users and

Installers of Industrial and Commercial Fans, provides ad-

ditional safety information. This publication can be obtained

from AMCA International, Inc. at: www.amca.org.

Greenheck Vari-Green Motor catalog provides additional

information describing the equipment, fan performance,

available accessories, and specification data.

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Web site: www.greenheck.com

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of

one year from the shipment date. Any units or parts which prove defective during the warranty period will

be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by

the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective

during this period, they should be returned to the nearest authorized motor service station. Greenheck

will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change

specifications without notice.

Warranty

Problem

Check that pressure taps are a minimum of 1.5 duct diameters upstream or

downstream from any dimensional change, elbow, damper or other obstruction.

Make sure there are no kinks or punctures in the tubing between the Constant

Pressure Control and the pressure taps.

Make sure there are no kinks or punctures in the tubing between the Constant

Pressure Control and the pressure taps.
Try algorithm gain set A or B.

A cutout percent value is only valid for a discreet pressure set point. When the

pressure set point is changed, the cutout percent value must be adjusted as well. It is

recommended that you make sure your pressure set point is correct before

continuing.

If the controller will not shut the fan off, verify that the cutout value is correct and that

the timer has started by looking for the flashing LED. If the flashing LED is not

displayed, then the cutout value needs to be adjusted. Remember the cutout value

should be set when there is no demand on the system.

If the controller shuts the fan off when there is demand on the system, the cutout

value is too high. Lower the value and observe the operation of the system.

Not holding setpoint pressure

Fan Speed is unstable

Fan Cutout not working properly

Potential Solution

Troubleshooting