Cutout Percent, Parameter P06

(Fan inlet control only)
Factory Default = 20%
20% = Cutout disabled, fan on continuously.
20% to 100% in 0.1% increments
The cutout feature can only be used if the system

utilizes powered fans such as bathroom fans or

dryers. It will not function properly if passive devices

are installed in the system such as motorized

dampers.
The cutout percent needs to be set if you would like

the exhaust fan to turn off when there is no demand

on the system. The default value is set at 20%. If the

exhaust fan is required to operate at all times, leave

the cutout percent value at 20%.
When the output percent is less than the cutout

percent, the cutout timer is activated (The timer

value is in parameter P07). After the time has

elapsed, the fan will shut off.
Note: A cutout percent value is only valid for a

discreet pressure set point. When the pressure

set point is changed, the cutout percent value must

be adjusted as well. It is recommended that you

make sure your pressure set point is correct before

continuing.

To set the cutout percent value, the following steps

need to be followed:
• Set normal operation and verify the system is

maintaining the desired pressure set point with

no other equipment (dryers, bathroom fans, etc.)

operating.

• After the pressure has stabilized at the set point,

press the Down/Decrease button to show the

percent output voltage. Take note of this value.

(The value will fluctuate slightly within +/- 2%. A

mental average will be adequate.)

• The recommended Cutout Value is 1-2

percentage points above the value you noted

in the previous step. See above for a graphical

representation.

When the system is running and the output percent

is less than the cutout value, the LED will flash.

After the cutout time has elapsed, the fan will turn

off. When the fan turns off, the display will show

“OFF” and the LED will flash.

Parameter Descriptions

Pressure Set Point, Parameter P01
Factory Default = -0.10 inches of water.
-1.00 to 1.00 inches of water in increments of 0.01

inches.

Auto Zero, Parameter P02
Factory Default = 0
0 = entry condition
1 = Perform Auto Zero
Auto zero sets the zero pressure reading of the

controller. Greenheck recommends performing auto

zero after installation and before first operation.
Place a piece of tubing from tubing connector “H” to

tubing connector “L”. Set value to 1 and press the

Enter button. The LED will turn white. Auto zero

is complete when the LED turns red. Remove the

tubing from the tubing connectors and reconnect the

pressure tap.

Factory Defaults, Parameter P03
Factory Default = 0
0 = entry condition
1 = Set all parameters to the factory default setting

Display Units, Parameter P04
Factory Default = 1
0 = Normal display is output percent
1 = Normal display is inches of water

Algorithm Gain, Parameter P05
Factory Default = 0
0 = Factory gains
1 = Gain set A
2 = Gain set B
If gain set 0 does not achieve stable operation use

one of the other sets to achieve stable operation.

Parameter

Description

Default Setting

P01

Pressure Set Point

-0.10 inches of water

P02

Auto Zero

0 (see below)

P03

Factory Defaults

0 (see below)

P04

Display Units

1 (inches of water)

P05

Algorithm Gains

0 (factory gains)

P06

Cutout Percent

20%

P07

Cutout Delay Timer

30 seconds

P08

Override Output Percent

100%

P09

Pressure Input Filter

0 seconds

P10

Start Up Timer

10 seconds

P11

Fan-Inlet/Fan-Outlet Control

1 (fan inlet control)