beautypg.com

Receiving, Unpacking, Handling – Greenheck Vari-Green Control - Constant Pressure Indoor (474766) User Manual

Page 2: Storage, Indoor only, Inspection and maintenance during storage, Installation and setup guide

background image

2

Receiving

Upon receiving the product check to make sure all

items are accounted for by referencing the bill of

lading to ensure all items were received. Inspect

each crate for shipping damage before accepting

delivery. Notify the carrier if any damage is noticed.

The carrier will make notification on the delivery

receipt acknowledging any damage to the product.

All damage should be noted on all the copies of

the bill of lading which is countersigned by the

delivering carrier. A Carrier Inspection Report should

be filled out by the carrier upon arrival and reported

to the Traffic Department. If damaged upon arrival,

file a claim with carrier. Any physical damage to

the unit after acceptance is not the responsibility of

Greenheck Fan Corporation.

Unpacking

Verify that all required parts and the correct

quantity of each item have been received. If any

items are missing, report shortages to your local

representative to arrange for obtaining missing

parts. Sometimes it is not possible that all items

for the unit be shipped together due to availability

of transportation and truck space. Confirmation of

shipment(s) must be limited to only items on the bill

of lading.

Handling

The motor amperage and voltage ratings must be

checked for compatibility to supply voltage prior

to final electrical connection. Wiring must conform

to local and national codes. Consult local code

authorities for specific requirements.

Storage

Product is protected against damage during

shipment. If the product cannot be installed and

operated immediately, precautions need to be

taken to prevent deterioration of the product during

storage. The user assumes responsibility of the

product and accessories while in storage. The

manufacturer will not be responsible for damage

during storage. These suggestions are provided

solely as a convenience to the user.

Indoor Only

Do not store this product outdoors. The ideal

environment for the storage of this product is

indoors, above grade, in a low humidity atmosphere

which is sealed to prevent the entry of blowing

dust, rain or snow. Temperatures should be evenly

maintained between 30° to 110°F (-1° to 43°C) (wide

temperature swings may cause condensation and

“sweating” of metal parts). All accessories must be

stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice, or

snow and wipe dry before moving to indoor storage.

Allow cold parts to reach room temperature to

avoid “sweating” of metal parts. To dry parts and

Parts Needed (Not provided by Greenheck)
• 18 - 20 gauge 3-wire plenum rated control wire

• 1/4 inch inside diameter plastic tubing

• Normally Open switch or relay for optional remote

override

Pressure Taps

Either room or duct pressure taps may be used. Be

sure to mount them in the room or duct system you

intend to control.
Be careful not to pinch or kink the pressure tubing

anywhere along its length.
Condensation running down the interior of the

pressure tubing may damage the controller’s sensor.

Forming a drip loop in the tubing just before it enters

the Greenheck Constant Pressure Controller is good

practice. (The distance from the bottom of the loop

to the controller’s pressure port should be one to two

inches [2.5 to 5 cm] greater than the highest static

pressure, including error conditions, in the system.)

Drip Loop

packages, use a portable electric heater to get rid

of any moisture buildup. Leave coverings loose

to permit air circulation and to allow for periodic

inspection. The unit should not be stored on the

floor.

Inspection and Maintenance

During Storage

While in storage, inspect product once per month.

Keep a record of inspection and maintenance

performed. If moisture or dirt accumulations are

found on parts, the source should be located and

eliminated.

Installation and Setup Guide

This guide provides instructions for how to

install, wire and program the control system for

use when constant pressure in a duct or room

system is required. This does not cover ductwork

recommendations or other considerations. When

installed, this control system will automatically vary

the speed of the fan to maintain a constant pressure

within the system.