beautypg.com

Constant pressure control, Wiring – Greenheck Vari-Green Control - Constant Pressure Indoor (474766) User Manual

Page 4

background image

4

Wall Mount
1. Using a 1/16” Allen wrench, separate the mount-

ing base and the cover by driving in the 1/16” Allen

screws until the cover comes free. Driving the

screws in prevents you from losing them.

2. Drill a ¾” hole in the drywall to relieve the pressure

fitting where the pressure tap is to be installed.

3. Place the mounting base pressure fitting in the ¾”

hole and align the mounting base to the wall.

4. Using a pencil, mark out the two mounting holes on

the wall.

5. Drill two 3/16” holes in the center of each marked

mounting hole. Insert a drywall anchor into each hole.

6. Pull the pressure tubing through the wall and out of

the 3/4” hole, leaving about two inches free.

7. Secure the pressure tubing to the pressure fitting.
8. Secure the base to the drywall anchors using the

#6 x 1 inch mounting screws provided.

9. Attach Cover by latching it to the top of the base,

rotating the cover down and snapping it into place.

10. Secure the cover by backing out the lock-down

screws using a 1/16” Allen wrench until they are

flush with the bottom of the cover.

Constant Pressure Control

• The Constant Pressure Control contains an

integral pressure transducer.

• Mount the Constant Pressure Control box in

an accessible location as close as possible to

the pressure tap and fan. Keep wiring lengths

between the Constant Pressure Control and the

fan to 200 feet or less. Keep pressure tubing

lengths between the Constant Pressure Control

and the pressure taps to 100 feet or less.

• Mount the Constant Pressure Control in the

vertical position with the tubing connectors in the

down position.

One Duct Tap – Maintains constant pressure

in duct based upon space pressure where the

Constant Pressure Control is mounted – Connect

the “H” tubing connector on the Constant

Pressure Control to the pressure tap using 1/4-

inch tubing. The “L” tubing connector remains

open to atmosphere.

One Duct Static Tap and One Duct Total Tap

Maintains a constant velocity pressure in a duct.

This allows the system to automatically adjust the

airflow in a system to compensate for filter or coil

loading. Connect the “H” tubing connector on the

Constant Pressure Control to the total pressure

tap and connect the “L” tubing connector to

the static pressure tap using 1/4” tubing. The

resultant measurement will be velocity pressure.

System Balancing – The Constant Pressure

Controller can maintain a velocity pressure from

0 to 1”. To balance the system, calculate the

velocity pressure required for the system based

on the intended CFM and duct area:

Where A is the duct area in ft

2

.

Set parameter P11=0 and parameter P01 (the

pressure setpoint) to the desired velocity

pressure. If airflow verification is needed, external

CFM measurements can be taken and the

velocity pressure can be adjusted until the

desired airflow is achieved.

One Room Tap – Maintains constant pressure in a

room based upon space pressure where the Con-

stant Pressure Control is mounted – Connect the “H”

tubing connector on the Constant Pressure Control

to the pressure tap using 1/4-inch tubing. The “L”

tubing connector remains open to atmosphere.

Two Room Taps – Maintains a constant

differential pressure between two rooms, allowing

the Constant Pressure Control to be mounted in a

remote location - Connect the “H” tubing connector

on the Constant Pressure Control to the pressure

tap in the high pressure room using 1/4-inch

tubing. Connect the “L” tubing connector on the

Constant Pressure Control to the pressure tap in

the low pressure room using 1/4-inch tubing.

• Make sure the tubing is not kinked or punctured.

Wiring

See diagram on page 7 for wiring overview.
• Control Box to Factory Mounted Transformer

Control Input

• Optional Remote Override:
Connect a normally-open switch between terminals

J3+ and J3- on the controller. Closing this switch will

activate the remote override feature. Opening the

switch will de-activate the override.

Controller

Terminal

Transformer

Control Input

J1 - POWER

to 24V

J1 - GROUND

to COM

J1 - OUTPUT

to 0-10V

Low-voltage

control wiring

Wall Mount

Mounting Plate

Cover