beautypg.com

Troubleshooting – Greenheck Vane Axial Fans (452954) User Manual

Page 9

background image

Problem

Cause

Corrective Action

Motor fails to start

Blown fuses

Replace fuses with proper type and rating.

Overload trips

Check and reset overload in starter.

Improper power supply

Check to see that power supplied agrees with motor
nameplate and load factor.

Improper line connections

Check connections with diagram supplied with motor.

Open circuit in winding or
control switch

Indicated by humming sound when switch is closed.
Check for loose wiring connections. Also verify all control
contacts are closing.

Mechanical failure

Check to see if motor and drive turn freely. Check bearings
and lubrication.

Short circuited stator

Indicated by blown fuses. Motor must be rewound.

Poor stator coil connection

Remove end bells, locate with test lamp.

Impeller defective

Look for broken bars or end rings.

Motor may be overloaded

Reduce load.

Motor stalls

One phase may be open

Check lines for open phase.

Wrong application

Change type or size. Consult manufacturer.

Overload motor

Reduce load.

Low motor voltage

See that nameplate voltage is maintained. Check
connection.

Open circuit

Fuses blown, check overload relay, stator and push
buttons.

Motor runs and then
dies down

Power failure

Check for loose connections to line, to fuses, and to
control.

Motor does not come
up to speed

Not applied properly

Consult supplier for proper type.

Voltage too low at motor
terminals because of line
drop

Use higher voltage on transformer terminals or reduce
load. Check connections. Check conductors for proper
size.

Starting load too high

Check what load motor is supposed to carry at start.

Broken impeller blade(s) or
loose impeller

Look for cracks near the rings. A new impeller may be
required as repairs are usually temporary.

Open primary circuit

Locate fault with testing device and repair.

Motor takes too long to
accelerate

Excess loading

Reduce load.

Poor circuit

Check for high resistance.

Defective motor

Replace with new motor.

Applied voltage too low

Get power company to increase power tap.

Wrong rotation

Wrong sequence of phases

Reverse connections at motor or at switchboard.

Motor overheats while
running under load

Overloaded

Reduce load.

Frame or bracket vents may
be clogged with dirt and
prevent proper ventilation of
motor

Open vent holes and check for a continuous stream of air
from the motor.

Motor may have one phase
open

Check to make sure that all leads are well connected.

Grounded coil

Locate and repair.

Unbalanced terminal voltage

Check for faulty leads, connections and transformers.

Troubleshooting

Your motor service and any troubleshooting must be handled by qualified persons who have proper tools and
equipment.

9

Vane Axial Fans

®