Heater – Greenheck TSU Direct Gas Manual (456857) User Manual

Page 8

background image

8

Heater

Symptom

Possible Cause

Corrective Action

Blower runs, heater tries

Cracked flame rod

Porcelain can be cracked. Replace

to light with visible spark,

flame rod.

and possibly pilot but
shuts down prior to

No gas to pilot

A. Check gas pressure

main fire.

B. Check pilot solenoid valve for

restrictions

C. Check pilot regulator for restrictions
D. Check for bend in aluminum pilot line,

repair or replace

Check for ground

A. Unit should be well grounded
B. Flame safeguard has a grounding

screw in it, check to see if it is
grounded. Pilot will not work if unit is
not grounded.

Dirty flame rod

Clean flame rod with emery cloth and
wipe porcelain clean.

Flame rod is grounded out

Check that flame rod is not touching
burner or that foreign debris is not
grounding out unit. Clean or adjust.

Blower runs,

High limit switch not

High limit should be set to 130°F.

high limit trips out

set correctly

Modulation device is not

Check modulation system and see

modulating

owners manuals for repair.

Blower runs, flame

High gas pressure not set properly

See startup instructions for

safeguard goes out on

setting high fire

safety after operating
or unit cycles on and off

Pilot regulator not set properly

Pilot is too large causing flame to go
past flame rod. Turn down gas pressure

Airflow too low or marginal for unit.

A. Adjust unit's CFMs to increase SP

Unit heats, lowering airflow

loss across burner

causing switch to open

B. Adjust baffles across burner to

increase SP

Microamps not steady with pilot on

A. Check wiring for spark rod and

flame rod

B. Check for cracks in porcelain on

flame rod. If present, replace

C. Soot buildup on flame rod

If present clean rod

Blower runs, unit heats,

Output temperature not set properly

See startup section for proper setting

Output air not warm
enough.

Main regulator not set properly

See setup section for setting high
fire on main regulator

Clogged vent orifice on regulator

Clean or replace vent

Supply pipe too small

Recheck pipe size going to unit and
repipe with larger pipe if necessary

Discharge bulb not sensing

Check placement, should be in

discharge air

blower discharge

Maxitrol System

Refer to Maxitrol manuals,

not functioning properly

make adjustments as manuals suggest

Supply pressure too low

Contact utility company