Direct Gas-Fired Heating
N/A
Gas regulator installed:
Regulator:
NG LP Supply pressure:
in. wg
High & low pressure switches installed:
High setting:
in. wg.
Typical 8 in. wg
Low setting:
in. wg
Typical 3 in. wg (Natural Gas)
Burner differential pressure:
in. wg
Between 0.625 and 0.675 in. wg
Set low fire time delay:
Between 75% of it’s max. setting.
Should provide at least 10 sec. of low fire while lighting.
Set max. firing rate:
Disconnect the wire connected to terminal #4 (Maxitrol 14)
Disconnect the wire connected to terminal #2 & #4 (Maxitrol 44)
Jumper terminals T1 & T2 (Maxitrol SC-25)
Adjust regulator to achieve design
T
Design T:
ºF
Set min. firing rate:
Disconnect one of the wires running to the modulating valve
Adjust minimum firing rate to provide continuous flame that covers both the flame rod and
the entire burner
Increase = CCW
Decrease = CW
Flame signal:
Honeywell = 1.25 VDC
BASO = 1.0 AMP
Signal:
Discharge air temp setting:
DAT Set point:
ºF
Comments:
Gas Pressure Chart
Direct Gas
Max. Inlet Gas Pressure
(natural gas or propane)
Min. Gas Pressure
(natural gas)
Min. Gas Pressure
(propane)
< 800 MBH
0.5 psi (14 in. wg)
7-12 in. wg
(output dependant)
3 in. wg
> 800 MBH
5 psi
0.5 psi (14 in. wg)
3 in. wg
Indirect Gas
High Fire
Low Fire
(staged control)
Low Fire
(2:1 modulating)
Low Fire
(4:1 modulating)
Natural Gas
3.5 in. wg
0.875 in. wg
0.875 in. wg
0.333 in. wg
Propane
10 in. wg
2.5 in. wg
2.5 in. wg
1 in. wg