Direct gas-fired heating n/a, Gas pressure chart – Greenheck Energy Recovery and Make-Up Air Start-Up Report User Manual

Page 7

background image

7

Direct Gas-Fired Heating

N/A

Gas regulator installed:

Regulator:

NG LP Supply pressure:

in. wg

High & low pressure switches installed:

High setting:

in. wg.

Typical 8 in. wg

Low setting:

in. wg

Typical 3 in. wg (Natural Gas)

Burner differential pressure:

in. wg

Between 0.625 and 0.675 in. wg

Set low fire time delay:

Between 75% of it’s max. setting.
Should provide at least 10 sec. of low fire while lighting.

Set max. firing rate:

Disconnect the wire connected to terminal #4 (Maxitrol 14)
Disconnect the wire connected to terminal #2 & #4 (Maxitrol 44)
Jumper terminals T1 & T2 (Maxitrol SC-25)

Adjust regulator to achieve design

T

Design T:

ºF

Set min. firing rate:

Disconnect one of the wires running to the modulating valve

Adjust minimum firing rate to provide continuous flame that covers both the flame rod and

the entire burner

Increase = CCW
Decrease = CW

Flame signal:

Honeywell = 1.25 VDC
BASO = 1.0 AMP

Signal:

Discharge air temp setting:

DAT Set point:

ºF

Comments:

Gas Pressure Chart

Direct Gas

Max. Inlet Gas Pressure

(natural gas or propane)

Min. Gas Pressure

(natural gas)

Min. Gas Pressure

(propane)

< 800 MBH

0.5 psi (14 in. wg)

7-12 in. wg

(output dependant)

3 in. wg

> 800 MBH

5 psi

0.5 psi (14 in. wg)

3 in. wg

Indirect Gas

High Fire

Low Fire

(staged control)

Low Fire

(2:1 modulating)

Low Fire

(4:1 modulating)

Natural Gas

3.5 in. wg

0.875 in. wg

0.875 in. wg

0.333 in. wg

Propane

10 in. wg

2.5 in. wg

2.5 in. wg

1 in. wg