Pdx cooling n/a – Greenheck Energy Recovery and Make-Up Air Start-Up Report User Manual
Page 4

4
PDX Cooling
N/A
Outdoor Air Temp.
________ºF
Condensing Fan 1
Condensing Fan 2
Condensing Fan 3
(If applicable)
Outdoor Air Wet Bulb ________ºF
L1 ____________ Amps
L1 ____________ Amps
L1 ____________ Amps
L2 ____________ Amps
L2 ____________ Amps
L2 ____________ Amps
L3 ____________ Amps
L3 ____________ Amps
L3 ____________ Amps
Compressor 1
Hot gas reheat valve closed
Compressor 1
Hot gas reheat valve open
(If applicable)
Compressor 2
(If applicable)
L1 ____________ Amps
L1 ____________ Amps
L1 ____________ Amps
L2 ____________ Amps
L2 ____________ Amps
L2 ____________ Amps
L3 ____________ Amps
L3 ____________ Amps
L3 ____________ Amps
Crankcase
heater _________ Amps
Crankcase
heater _________ Amps
Crankcase
heater _________ Amps
*Reference locations on next page.
Cooling
HP Heating
Cooling
Cooling
HP Heating
A. Discharge Pressure (psi)
*P1
B. Discharge Pressure Converted to
Temperature (ºF)
C. Liquid Line Temperature (ºF)
*T1
D. Subcooling (ºF)
(B-C)
Should be between 12º and 17ºF
E. Suction Line Pressure (psi)
*P2
F. Suction Line Temperature (ºF) *T2
G. Suction Pressure Converted to
Temperature (ºF)
H. Superheat (ºF)
(F-G)
Should be between 8º and 12ºF
Water In (ºF)
*T3
Water Out (ºF)
*T4
Hot Gas Bypass Operational
(Not present on digital scroll compressors)
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Suction Pressure Set Point
Compressor Sight Glass (if present)
Oil Level
Oil Foaming
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Comments:
NOTE
Refrigeration System Start-Up Checklist must be
performed by a Qualified Refrigeration Technician.
If a digital scroll compressor is installed in the unit,
make certain that all current readings are taken when
compressors are running under load. See the Digital
Scroll Compressors section in the unit IOM.
WARNING
All motor(s) / compressor(s) have been checked for
rotation. If blower rotation is incorrect, wiring must
be changed at the disconnect to ensure all motor(s) /
compressor(s) are corrected.
Operation of scroll compressor(s) in this unit are
directional and will be damaged if run in the wrong
direction.