Packaged DX Module for Make-Up Air Unit

NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical
supply.
The first step is to check airflow conditions. (e.g. improper ductwork, atypical wet bulb / dry bulb, etc.) After these
steps have been eliminated, proceed with troubleshooting by following this guide:

Troubleshooting – Refrigeration Circuit

TROUBLESHOOTING NOTE

Before any components are changed on the
refrigeration system, the cause of the failure must be
determined. Further problems will exist unless the
true cause or problem is identified and corrected.

IMPORTANT

Do not release refrigerant to the atmosphere! If
required service procedures include the adding or
removing of refrigerant, the service technician must
comply with all federal, state and local laws. The
procedures discussed in this manual should only be
performed by a qualified EPA Certified Technician.

Symptom Possible Cause

Corrective Action

Compressor
will not run
or does not
start

Open disconnect switch or circuit
breaker.

Close switch and/or breaker.

Compressor contactor not closing.

Check voltage to contactor coil, transformer, slave relay,
system. Replace parts as necessary.

Blown fuse or tripped breaker.

Check for shorted wire or motor. Replace fuse after
correcting problem.

Low line voltage.

Check line voltage. If more than 10% from compressor
marking, correcting is necessary.

Compressor motor protector open.

Motor thermal protector automatically resets. Allow time
(2 hours) for compressor to cool down so protector will
reset. Restart and check for reason overheat occurred.

Compressor defective.

Check motor for open circuit, short circuit, grounded
windings, or burn out. Compressor may be seized; check
refrigerant. If necessary, replace compressor.

High pressure switch open
or defective.

If manual reset (high pressure), reset switch. (Switch
opens at 600 psi and will not reset above 420 psi for
R-410A). Replace if defective.

Low pressure switch open
or defective.

Switch will open at 50 psi and auto-close at 90 psi.
Replace if defective.

Open room thermostat or control.
(No cooling required).

Check room temperature. If temperature is proper, wait
for thermostat to close.

Loose wiring.

Check all wire terminals and tighten as necessary.

Compressor
starts but
cuts out on
low pressure

Low pressure

switch

activates at

50 PSIG

Low or loss of refrigerant charge.

Check refrigerant pressures and temperatures
(subcooling.)

Airflow restricted.

Check for dirty evaporator coil, dirty filters, dampers
closed, iced evaporator coil, improper belt, check motor
amps, check duct design.

Restriction in refrigerant line.

Check refrigerant pressures, look for frosted tubing and
components indicating a restriction. Check pressure drop
across the filter drier.

Defective low pressure switch.

Replace.

Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service