8

MiniCore

SPECIAL TOOLS

• Voltmeter
• Incline manometer or equivalent
• Tachometer
• Amperage meter

System Start-Up

DANGER

Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.

CAUTION

Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.

CAUTION

Do not operate without the filters installed. They
prevent the entry of foreign objects such as leaves,
birds, etc.

CAUTION

Do not run unit during construction phase. Damage to
internal components may result and void warranty.

WARNING

Do not jumper any safety devices when operating the
unit. This may damage components within or cause
serious injury or death.

Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.

Unit Documentation Record

Unit Model No. __________________________________

Unit Serial No. ____________________________________

Start-Up Date ____________________________________

Start-Up Personnel Name _________________________

Start-Up Company ________________________________

Phone Number ___________________________________

Pre-Start-Up Checklist

†Disconnect and lock-out all power switches.
† Remove any foreign objects that are located in the

energy recovery unit.

† Check all fasteners, set-screws, and locking collars

on the fans, bearings, drives, motor bases and
accessories for tightness.

† Filters can load up with dirt during building

construction. Replace any dirty pleated filters.

† Verify that non-motorized dampers open and close

properly.

† Check the tightness of all factory wiring

connections.

† Verify control wire gauge.

Line Voltage. Check at unit disconnect.

L1-L2

Volts

Motor Amp Draw

Supply Motor Amps

L1

Amps

L2

Amps

Exhaust Motor Amps

L1

Amps

L2

Amps

Fan RPM

Supply Fan RPM

Exhaust Fan RPM

Correct fan rotation direction?

Supply Fan

Yes / No

Exhaust Fan

Yes / No

Start-Up Checklist

®