Troubleshooting – Greenheck MiniCore (479677) User Manual

Page 11

background image

11

MiniCore

Symptom

Possible Cause

Corrective Action

Unit is NOT
operating

Electrical

Check fuses/circuit breakers, replace if needed. Check for On/
Off switches. Check for correct supply voltage.

Motor

Check motor horsepower is correct and not tripping overloads.

Excessive noise

Fan wheel rubbing on inlet

Adjust wheel and/or inlet cone. Tighten wheel hub or bearing
collars on shaft.

Bearings

Replace defective bearing(s). Lubricate bearings. Tighten collars
and fasteners.

Wheel out of balance

Clean, replace or rebalance.

Low airflow (cfm)

Fan speed too low

Increase fan speed.

Dirty filters or energy core

Replace filters and/or follow the cleaning procedures.

High static pressure

Incorrect fan-to-duct connections. Make sure dampers open
appropriately. Increase fan speed

High airflow (cfm)

Fan speed too high

Decrease fan speed.

Low static pressure

Make sure grilles, filters and access doors are installed.
Decrease fan speed.

Always provide the unit model and serial number when requesting parts or service information. Always check
motor amps and compare to nameplate rating.