7.

Calibration - Initial Settings - Cam Changes

Initial Settings

The factory settings provide the positioner with an initial
range of settings that will allow the operation of position-
ers on most applications.

Signal Input

- 0.2 to 1.0. bar. (3-15 psi).

Range

- 0% to 100%

Control Function - Linear.
Action

- Direct Acting.

(Opening on increasing Signal in
CCW-direction).

The F10 positioner is provided with the following features
for making changes to the initial settings:

Zero

By the external zero adjustment screw.

Range

By the internal range adjustment ring.

Range Spring The standard range spring is suitable for

normal operation and split ranging.

Cam Segment Six segments are provided for the rotary

positioner and eight segments for the
linear positioner (see table).

Cam Changes
Remove the cover and indicator from the positioner
exposing the Cam. The Cam is double sided: CCW for
direct acting, CW for reverse acting.

If the actuator is fully clockwise and the actuator is to
rotate CCW on instrument signal increase, the Cam
should be on the “CCW” side and the start marking
should be in line with the Cam Follower Bearing. If the
actuator is fully counterclockwise and the actuator is to
rotate CW on instrument signal increase, the Cam should
be on the “CW” side and the start marking should be in
line with the Cam Follower Bearing.

If the cam is not in the correct position, change as fol-
lows:

1. Remove the cam nut (1).
2. Re-install the cam plate in the correct position, taking

care that the correct segment is adjacent to the cam
follower (2).

3. Replace the cam nut and fix it.
4. Replace the indicator disk, taking care that it in the

correct position.

90°

Standard setting

CCW Direct

CW Reverse

Initial settings

1.0 bar

0.2 bar

0

Cam Segment

Rotary actuator

Linear actuator

90° CCW

90° CW

40° CCW

40° CW

lin

lin

lin

lin

=%

=%

=%

=%

QO

QO

QO

QO

*

*

SR

SR

lin

= linear

=% = equal percentage
QO = Quick Opening
SR = Split Range
*

= Special cam split range

Top view of cam

Rotary actuator

Cam 90°

Linear actuator

Cam 40° (49°)

1

2