Installation - Linear Actuators

Pneumatic Connections - Double acting

Assuming a standard installation, direct acting with an
increasing signal to open the valve (rising spindle).

Before connecting any air supply make sure that
the air available is clean dry instrument air filtered
to at least 25 microns.

1. Connect an appropriate piece of air tubing between

the port 1. on the positioner to the “A” port on the
actuator. (The “A” port is the one that, when air is
applied to it, opens the valve).

2. Connect an appropriate piece of air tubing between

the port 2. on the positioner to the “B” port on the
actuator. (The “B” port is the one that when air is
applied to it, closes the valve).

3. Connect an air supply to the positioner port marked

“S”.

4. If the positioner is required to meet enclosure rating

IP54, be sure that the "Exhaust" port is connected
with elements which prevent the input of water and
give no pressure rising inside the housing because
of throttling of exhaust flow (no sintered filters, but a
piece of tube or a special IP65 Exhaust plug with
diaphragm

5. Connect port "Instrument" with pneumatic input

signal.

Note: For a reverse acting assembly, both the air

connections and the cam must be reversed -
see page 7.

Pneumatic Connections - Single acting

Assuming a standard installation, with direct acting an
increasing signal to open the valve (rising spindle).

Before connecting any air supply make sure that
the air available is clean dry instrument air filtered
to at least 25 microns.

1. Connect an appropriate piece of air tubing between

the port 1. on the positioner to the “A” port on the
actuator. (The “A” port is the one that when air is
applied to it, opens the valve).

2. Connect an air supply to the positioner port marked

“S”.

3. If the positioner is required to meet enclosure rating

IP54, be sure that the "Exhaust" port is connected
with elements which prevent the input of water and
give no pressure rising inside the housing because
of throttling of exhaust flow (no sintered filters, but a
piece of tube or a special IP65 Exhaust plug with
diaphragm

Double acting

Single acting

4. Connect port "Instrument" with pneumatic input

signal.

Note: For a reverse acting assembly, both the air

connections and the cam must be reversed -
see page 7.