13 Frequently Asked Questions
Q: I set the Final Value Cutoff Low at 5 percent. How will the 
positioner operate?
A: Assume that the present command signal is at 50 percent. If the 
command signal is decreased, the positioner will follow the command 
until it reaches 5 percent. At 5 percent, the spool will be driven fully 
open or fully closed, depending on the air action of the valve, in order 
to provide full actuator saturation and tight shutoff. The positioner 
will maintain full saturation below 5 percent command signal. As the 
command increases, the positioner will remain saturated until the 
command reaches 6 percent (there is a 1 percent hysteresis value 
added by the positioner). At this point, the stem position will follow 
the command signal. While in Final Value Cutoff, the Logix 3400MD 
LEDs will blink GGGY.
Q: I have Final Value Cutoff set to 3 percent but the valve will not 
go below 10 percent.
A: Is a lower soft stop enabled? The lower soft stop must be less than 
or equal to zero percent in order for the Final Value Cutoff to become 
active. If a positive lower soft stop is written, this stop will take 
priority over the Final Value Cutoff feature. When the lower soft stop 
is reached, the positioner will blink a GYGYs code.
Q: Will soft stops prevent the valve from going to its fail position?
A: No.
Q: What is the difference between a model with Standard 
diagnostics and a model with Advanced diagnostics?
A: The model with Advanced diagnostics adds top and bottom 
actuator pressure sensors. This allows for more diagnostic 
calculations such as loss of pressure, friction, advanced signatures, 
and troubleshooting. The pressure sensors, if present, are also used 
in the positioner control algorithm to enhance valve stability.
Q: Can I upgrade from a Standard to an Advanced?
A: Yes. Referencing the IOM, an advanced pressure sensor board 
assembly can be purchased. Simply replace the pressure sensor plug 
plate with the advanced pressure sensor board. Perform an actuator 
pressure calibration.