Flowserve UEX Limitorque User Manual
Page 53

53
Limitorque UEX FCD LMENIM1205-03-AQ – 05/15
flowserve.com
Table 16.3 – Belden Cable Specifications
Belden
Part No.
AWG
(Stranding)
dia. Inches
Nom. DCR
Insulation
material
(color code)
Nominal
O.D.
Nom
Impedance
(ohms)
Nominal
Capacitance
Test
Frequency
(MHz)
Maximum
Attenuation
dB/100ft
3082A
2 – 15 AWG
(19 x 28)
3.6 ohm/1000 ft
11.8 ohm/km
Power pair
(Black/Red)
12.2 mm
120
12.0 pF/ft
0.125
0.5
1
0.13
0.25
1.36
2 – 18 AWG
(19 x 30)
6.9 ohm/1000 ft
22.7 ohm/km
Data pair
(Blue/White)
3084A
2 – 22 AWG
(19 x 34)
17.5 ohm/1000
ft
57.4 ohm/km
Power pair
(Black/Red)
7.2 mm
120
12.0 pF/ft
0.125
0.5
1
0.29
0.50
1.70
2 – 18 AWG
(19 x 36)
28.0 ohm/1000
ft
91.9 ohm/km
Data pair
(Blue/White)
Table 16.4 – Total Cable Length Between Repeaters or Nodes:
Network Size
125 KBPS
250 KBPS
500 KBPS
Thick Trunk Length
500 m (1,640 ft)
250 m (1,640 ft)
100 m (1,640 ft)
Thin Trunk Length
100 m (328 ft)
100 m (328 ft)
100 m (328 ft)
Flat Trunk Length
380 m (1,250 ft)
200 m (656 ft)
75 m (246 ft)
Maximum Drop Length
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
Cumulative Drop Length
156 m (512 ft)
78 m (256 ft)
39 m (128 ft)
Note: Each actuator includes 0.60 meters of internal drop length.