10.1 Local Features
LCD Displays – The LCD displays an array of data concerning the status of actuator components
in clear, graphical or textual language. The UEX is available with eleven languages:
English, Spanish, German, French, Italian, Portuguese, Mandarin, Russian, Bahasa
Indonesia, Turkish and Katakana.
Normal Display – The normal display illustrates current valve position and status.
Alarm Functions – Alarm functions (active alarms will be toggled every four seconds)
that may be displayed include:
• Valve Jammed - Valve cannot start moving
• Lost Phase - One of three phases lost
• Motor Overtemp – Thermal overload exceeded
• Overtorque - Torque exceeded in mid-travel
• Hardware Failure - Indication
• Modbus, Profibus, F
oundation
Fieldbus, DeviceNet off - Enabled, but “OFF”
• ESD Active - ESD signal active
• Inhibit Active - Inhibit signal present
• No analog signal - 4–20 mA signal absent (Modutronic enabled, red selector switch in
“REMOTE”)
• DDC, PB, FF, DNet comm. Loss – Enabled, signal absent
• Analog Output Loss - Enabled, but output current loop open