Worcester actuation systems – Flowserve DFC17 User Manual
Page 27
![background image](https://www.manualsdir.com/files/784826/content/doc027.png)
WCAIM2026
DataFlo Digital Electronic Controller DFC17 Installation, Operation and Maintenance Instructions
27
Flow Control Division
Worcester Actuation Systems
continued from previous page
CHECK
ACTION
NOTES AND CAUTIONS
6.3.10
Check temperature of motor(s).
Allow the motor(s) to cool so that
Duty cycle is specified at an ambient
One AC motor has a thermal cutout
the thermal switch can reset.
temperature of 70°F, 60 Hz.
switch built in that opens at about
Normally the thermal switch
210°F (winding temperature). If the
will not open unless the motor’s
thermal cutout has opened, both motors
rated duty cycle is exceeded
are deenergized until the thermal switch
and/or the ambient temperature
resets (20-2375 sizes).
is very high. Correct the problem.
6.3.11
Check the operating torque of the valve. If
If operating torque of valve exceeds
If the actuator is removed from a
necessary, remove the actuator from the valve.
the specified torque for the seats
three-piece valve that requires the body
Measure valve torque with an accurate torque
used and the DP across the
bolts to also be removed, the valve
wrench. Check torque under actual operating
valve, determine cause and
body bolts must be retorqued to
conditions if possible.
correct. If torque falls within
specifications before checking valve
normal range, it is possible that
torque. See Valve IOM.
the actuator is undersized.
6.3.12
Check ambient temperature.
Actuator duty cycles are
Higher ambient derates duty cycle.
specified at an ambient
temperature of 70°F.
6.3.13
Check to see that mechanical brake is
Replace defective mechanical
All 2" CPT valves with Controller
operating correctly.
brake. If one was never installed,
boards in actuator must have
order a kit and install it in actuator.
mechanical brake installed
to prevent oscillation.
6.3.14
Check to see if actuator can move a high
If motor(s) cannot start, go to next
torque valve from a stop under load when
larger size actuator.
moving in the same direction as last command
(mechanical brake does not allow motor(s) to
unwind).
6.3.15
Check to see which direction of travel
Replace circuit board.
causes problem. If actuator is coming off
open limit switch (traveling CW) when it slows
down or stops, then either Q1 or U1 is bad.
If actuator is coming off closed limit switch
(traveling CCW), then either Q2 or U2 is bad.
(AC boards only)