Worcester actuation systems – Flowserve DFC17 User Manual
Page 13
WCAIM2026
DataFlo Digital Electronic Controller DFC17 Installation, Operation and Maintenance Instructions
13
Flow Control Division
Worcester Actuation Systems
Table 4.1.1 Run Mode Menu
Display
Description
Units
Pr1
Process #1 signal value.
Engineering
Pr2
Process #2 signal value.
Engineering
Pr12
Average of process #1 and process #2 signal values.
Engineering
SEt -
Setpoint value. Only one of the following will be displayed:
Engineering
SEtA – analog setpoint; SEtP – digital setpoint;
SEtL – local manual setpoint.
PtEr
Proportional term value.
itEr
Integral term value.
dtEr
Derivative term value.
ALr
Alarm. Alarm shown is highest priority. See Mode Change
Key Sequence table.
POS
Valve position.
Percent
CYCn
Number of cycles.
Times 1000
cycles
PHi
Highest recorded process value.
Engineering
PLo
Lowest recorded process value.
Engineering
Table 4.1.2 Mode Change Key Sequence
Press Key(s) for Three Seconds
Mode Entered
SEL
Program Mode.
SEL + DN
Calibration Mode.
SEL + UP
Manual Setpoint Mode.
SEL + DN + UP
Manual Position Mode (gives access to Auto Tuning).
Table 4.1.3 Alarm Displays
Display
Description
PrHi
Process high limit alarm.
PrLo
Process low limit alarm.
Hi
Shaft upper position alarm.
Lo
Shaft lower position alarm.
SHFt
Invalid shaft position alarm.
Pro
Invalid process value alarm.
SEt
Invalid setpoint value alarm.
thEr
Motor driver circuit thermal warning alarm (DC motors only).