Flowserve Limitorque MX DeviceNet Field Unit User Manual
Page 9
9
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
Table 1.1 – Network specifications
Network Size
Up to 63 Nodes
Network Length
Selectable end-to-end network distance varies with speed
125 Kbps 500 m (1,640 ft)
250 Kbps 250 m (820 ft)
500 Kbps 100 m (328 ft)
Bus Topology
Linear (trunkline/dropline); power and signal on the same network cable
Bus Addressing
Multi-Master and Master/Slave special case; polled of change-of-state
(exception-based)
System Features
Selectable end-to-end network distance varies with speed
Termination resistor (121 ohms) must be used at each end of the network
1.5.1.2 MX Field Unit Specifications
CIP Generic Device Profile (Device Type = 00hex) extended to DNFU requirements
•
Group 2 Server
•
UCMM capable device
•
Predefined Master/Slave Connection Set supporting
•
Explicit Connection
•
Polled I/O Connection
•
Bit-Strobed I/O Connection
•
Change of State / Cyclic I/O Connection
•
Full support of fragmentation protocol
•
Device Heartbeat Message
•
Device Shutdown Message
•
Offline Connection Set
•
Galvanical Isolation: The isolation voltage for the DNFU is up to 1,500 VRMS for 1 minute (1,800
•
VRMS for 1 second
Power Supply: The DNFU Interface will be powered from the DeviceNet bus. A switching regulator is
•
used to generate the internal supply voltage: VCC nominal 5.0 V ± 5 %
Surge Suppression: The DNFU Interface is equipped with surge suppression for the DeviceNet
•
network data and power lines. Surge suppression is compliant with IEC 61000-6-2:2001.
Environmental conditions
The DNFU environmental parameters are within the same environmental constraints as the actuator.