4 di_actuator_faults_2_chan, 5 di_actuator_alarms_chan – Flowserve Limitorque MX DeviceNet Field Unit User Manual
Page 22
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
22
Table 4.16 – Possible values of DI_Actuator_Faults_1_Chan
Value
Definition
0x01
Monitor Relay
0x02
Valve Jammed
0x04
Manual Moved
0x08
Over Torque
0x10
Phase Error
0x20
Motor Over Temperature
0x03
Monitor Relay + Valve Jammed
0x05
Monitor Relay + Manual Moved
0x09
Monitor Relay + Over Torque
0x11
Monitor Relay + Phase Error
0x21
Monitor Relay + Motor Over
Temperature
0x07
Monitor Relay + Valve Jammed +
Manual Moved
0x13
Monitor Relay + Valve Jammed +
Phase Error
0x23
Monitor Relay + Valve Jammed
Motor Over Temperature
4.2.4 DI_Actuator_Faults_2_Chan
Table 4.17
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Close
Torque
Switch Fault
Open Torque
Switch Fault
Manual
Moved
Valve
Jammed
Phase Error Thermal
Overload
Table 4.18 – Possible values of DI_Actuator_Faults_2_Chan
Value
Definition
0x01
Thermal Overload
0x02
Phase Error
0x04
Valve Jammed
0x08
Manual Moved
0x10
Open Torque Switch Fault
0x20
Close Torque Switch Fault
0x03
Thermal Overload + Phase Error
0x05
Thermal Overload + Valve Jammed
0x09
Thermal Overload + Manual Moved
0x18
Manual Moved + Open Torque Switch Fault
0x28
Manual Moved + Close Torque Switch Fault
4.2.5 DI_Actuator_Alarms_Chan
Table 4.19
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Move Test
Active*
Not in
Remote
Close Inhibit
Active
Open Inhibit
Active
Remote ESD
Active
Local ESD
Active
* Available with Revision 1 to DeviceNet board.