2 devicenet field unit – Flowserve Limitorque MX DeviceNet Field Unit User Manual
Page 11
11
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
The MX features include:
Non-intrusive setup
•
Separately sealed terminal chamber
•
Absolute encoder for valve position sensing (no battery required)
•
32-character LCD for indication and calibration with configuration permitted in six languages.
•
Sophisticated electronic control, monitoring, and diagnostic capabilities with LimiGard™
•
technology
2.2.2 DeviceNet Field Unit
The DeviceNet field unit is installed in the MX controls compartment. This unit permits the actuator to
be controlled by a host controller, typically a PLC, via the DeviceNet network. The DNFU includes two
high-level, surge-protected, and isolated network communication channels, configurable digital I/O, and
configuration via LCD screen. The following commands and information may be transmitted over the
DeviceNet network:
“OPEN,” “STOP,” and “CLOSE” commands
•
“ESD” and “MOVE–TO” position commands
•
Actuator status and alarm messages
•
Six digital inputs and two analog inputs for user
•
A surge-protected and isolated communication channels
•
MX control panel configuration
•
Torque output (for reference only) and position feedback
•
Four digital outputs (standard)
•
Figure 2.2 – DeviceNet Field Unit