1 identity object instance attributes – Flowserve Limitorque MX DeviceNet Field Unit User Manual
Page 29

29
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
Table 4.34
Bit 15 - 11
Bit 10 - 9
Bit 3
Unused
Scaling 0 =
0 – 100 1 =
0 – 255 2 =
0 -4095 3 =
Reserved
Unused
4.4.1 Identity Object Instance Attributes
Table 4.35 – Identity Object Instance Attributes
Attribute
ID
Access Rule Name
Data Type Description of
Attribute
Semantics of Value
1
Get
(NV-RO)
Vendor ID
UINT
Identification of
each vendor by
number
966 (3C6hex)
(Note 1)
2
Get
(NV-RO)
Device Type
UINT
Indication of general
type of product
00hex
(Generic Device)
3
Get
(NV-RO)
Product Code
UINT
Identification of a
particular product
of an individual
vendor
19800 (4D58hex)
(Note 2)
4
Get
(NV-RO)
Revision
STRUCT
of
Revison of the item
the Identity Object
represents
1.1
(Note 3)
Major Revision
USINT
Major Revision of
DeviceNet
Limitorque Interface
Minor Revision
USINT
Minor Revision of
DeviceNet
Limitorque Interface
5
Get
(V-RO)
Status
WORD
Summary status of
device
(Note 4)
6
Get
(NV-RW)
Serial Number
UDINT
Serial number of
device
(Note 5)
7
Get
(NV-RW)
Product Name
SHORT_
STRING
Human readable
identification
”Flowserve MX”
(Note 6)
8
Get
(V-RO)
State
USINT
Present state
of the device as
represented by
the state transition
diagram
10
Get/Set
(NV-RW)
Heartbeat Interval
USINT
The nominal interval
between heartbeat
messages in
seconds
The default value
is 0. Zero disables
transmission of the
heartbeat message.
100
Get
(V-RO)
EEPROM Failure
BOOL
Result of EEPROM
checksum
verification
0 = EEPROM contents
is o.k.
1 = EEPROM contents
may be defective due
to checksum error
The further optional attributes
Configuration Consistency Value (Attribute ID 9)
•
Active Language (Attribute ID 11)
•
Supported Language List (Attribute ID 12)
•