2 output assembly instances – Flowserve Limitorque MX DeviceNet Field Unit User Manual
Page 17

17
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
An output is a signal produced at the PLC and sent to the actuator via the
•
network.
The user may select one output and one input instance.
The default assembly objects are as follows: Polled input - 105, Polled output - 100, Bitstrobe - 107,
COS - 109.
Table 4.1
Instance ID
Type
Data Component Name
Size
100
Output
Output 1 (All Control Channels)
9
101
Output
Output 2 (Analog Control and ESD only)
5
102
Output
Output 3 (Discrete Control and ESD only)
4
103
Output
Output 4 (Analog Control only)
3
104
Output
Output 5 (Discrete Control only)
3
105
Input
Input 1 (All Status Information)
16
106
Input
Input 2 (Position and Faults only)
6
107
Input
Input 3 (Position and Faults only)
8
108
Input
Input 4 (Position, User and Faults only)
11
109
Input
Input 5 (Faults and Alarms only)
6
4.2 Output Assembly Instances
Table 4.2 – Output Assembly Instance 100
Assembly
Object
Instance ID
Data
Component
Name
Class
Instance
ID
Attribute
ID
Name
ID
Name
Data
Type
100
Output 1
100
Channel
Interface
1
20
Ctrl_Status_Chan
BYTE
100
Channel
Interface
1
1
AO_Ctrl_Valve_ Flow_Chan INT
100
Channel
Interface
1
9
DO_Position_Chan
BYTE
100
Channel
Interface
1
21
DO_ESD_Poll_Cnxn
BOOL
100
Channel
Interface
1
11
DO_Relay_Chan
BYTE
100
Channel
Interface
1
18
DO_Move_Test_Chan
BOOL
100
Channel
Interface
1
19
AO_Analog_Output_Chan
UNIT
Table 4.3 – Output Assembly Instance 101
Assembly
Object
Instance ID
Data
Component
Name
Class
Instance
ID
Attribute
ID
Name
ID
Name
Data
Type
101
Output 2
100
Channel
Interface
1
20
Ctrl_Status_Chan
BYTE
100
Channel
Interface
1
1
AO_Ctrl_Valve_ Flow_Chan INT
100
Channel
Interface
1
21
DO_ESD_Poll_Cnxn
BOOL
100
Channel
Interface
1
10
DO_Move_Test_Chan
BOOL