Specifications – Flowserve APEX A9000 Accord User Manual
Page 4
![background image](https://www.manualsdir.com/files/784790/content/doc004.png)
4
5. Specifications
5.1 Technical data
Input signal
4-20 mA Current supply min.
3,6 mA
Current supply Max.
150 mA
Load Standard
400 ohm at 20mA Load HART
470 ohm at 20mA
Voltage dropStandard
8 VDC at 20mA Voltage drop HART
9.4 VDC at
20mA Angle of rotation min
0-40°
Angle of rotation Max
0-90°
Air supply range
1.5
– 6 bar
Out put
0-100% of air supply pressure
Air supply quality
Free from oil, dust and moisture IEC 770,
ISA 7.0.01
Air supply effect
<0.1%FS for10% pressure change at 6 Bar
Ingress protection
IP66 / Nema 4X
Operating humidity
0-100% rh non-condensing
Air connections
1/4” NPT
Cable entry
2 x 1/2” NPT or 2 x M20x 1,5
Terminals
Screw terminals 2,5 mm
2
(AWG 14)
Operating Temperature
-20 to +85°C-40 to +85°C (optional)
Storage temperature
-40 to +85°C
Air delivery capacity
7 Nm
3
/h @ 6 bar (3 bar diff pressure)
Air delivery capacity Double acting
7 Nm
3
/h @ 6 bar (3 bar diff pressure)
Air consumption Single acting
0,120 Nm
3
/h @ 6 bar
Air consumption Double acting
0,120 Nm
3
/h @ 6 bar
Cv air delivery Single acting
0,12
Cv air delivery Double acting
0,12
Cut off function
Close 0.5% Open 99.5%
Linearity
<1%
Sensitivity
<0.05%
Resolution
<0,1%
Repeatability
<0.2%
Hysteresis + dead band
<0.5%
Temp effect
<0.1%/10K
Mounting position effect
<0,2%
CE
93/68/EEC, 2004/108/EEC, 2006/95/EEC
Approvals
Ex II G Ex ia IIC T4 Ta: 85°C
Class I Division 2 Groups A,B,C,D T4 non-incendive with fieldwiring
Class I Division 2 IIC T4 non-incendive with fieldwiring
I.S. Class I Division 1 Groups A,B,C,D T4
I.S. Aex ia IIC T4
Certificate nr
Nemko 08ATEX1362X
Housing material
Die cast Aluminium
Surface treatment
Powder coating
Soft goods
Nitrile
Weight
1,5 kg (3.0 kg Explosion proof version)