Flowserve APEX A9000 Accord User Manual
Page 25

25
The Status Menu is used to select whether or not the positioner is in service.
The menu contents are shown in the figures on the right and the various
texts are described below:
o o service
Not in service.
Flashing indicator in upper left-hand corner of display.
in service
Positioner in service.
Critical parameters cannot be changed.
The Setup Menu is used for various settings.
The menu contents are shown in the chart on the next page and the various texts are described below:
Actuator
Type of actuator
Size of actuator
Time out
Rotating
Rotating actuator.
Small
10 s
Linear
Linear actuator.
Medium
25 s
Large
60 s
Extra Large
180 s
Lever
Only for linear actuator.
Lever stroke Stroke length to achieve correct display.
Level cal
Calibration of positions to achieve correct display.
Direction
Direct
Direct function (signal increase opens). Indicator/spindle rotates counter- clockwise.
Reverse
Reverse function.
Character
Curves that show position as a function of input signal.
FULL MENU
SETUP
SIGNAL
R
OT
AT
ION
Q
O
Sqr
Lin
Eq%
Linear
Equal %
Quick Open
Square Root
Custom Create Own Curve
Custom Characterization # of points (Specify # of pts, 3,5,9,17 or 33)
Custom Curve: Enter values on X and Y axis.
Current Range: 0%=4mA
, 100%= 20mA
Possibility of selecting which input signals correspond to 0% and 100%
movement respectively. Examples of settings: 4mA = 0%, 12mA =
100%, 12mA = 0%, 20mA = 100%
See Diagram
FULL MENU
STATUS