Flowserve APEX A9000 Accord User Manual
Page 28

28
Limit 2
See Limit 1.
temp
Alarm based on temperature.
On/Off
Temperature alarm on/off.
Low temp
Temperature low limit setting
High temp
Temperature high limit setting
Hysteresis
Allowed hysteresis.
Alarm on
Select ON/OFF offers output on terminals.
Valve act
Behaviour of valve when alarm is generated
Valve act
No action
Alarm generated only. Operations no affected.
Goto open
C+ gives full pressure and valve moves to fully open position. Positioner
changes to position Manual.
Goto close
C- gives full pressure and valve moves to fully closed position. Positioner changes to
position Manual.
Manual
Valve stays in unchanged position. Positioner moves to position Manual.
Alarm limit 1 on
Alarm limit 2 on
Alarm limit 1 off
Alarm limit 2 off
Alarm limit 2 on
Alarm limit 2 off
Alarm limit 1 off
100%
0%
Limit 1 max
Hysteresis
Limit 2 max
Hysteresis
Hysteresis
Limit 2 min
Hysteresis
Limit 1 min
Alarm limit 1 on