6 max power up temperature, 7 min power up temperature, 8 humidity percent – Flowserve Logix 520MD+ DD User Manual
Page 8: 6 health data, 1 valve health % warning, 2 actuator health % warning, 3 positioner health % warning, 4 control health % warning, 7 diagnostic values, 1 friction

DD User Manual - Logix® 520MD+ Series Digital Positioner FCD-LGENSF0013-01
© Flowserve Corporation
8
 
 
View the minimum temperature the positioner has seen since 
the last factory reset was performed. 
3.5.6
Max Power Up Temperature
View the maximum temperature the positioner has seen 
since the last time the positioner was powered up. 
3.5.7
Min Power Up Temperature
View the minimum temperature the positioner has seen since 
the last time the positioner was powered up. 
3.5.8
Humidity Percent
View the current relative humidity inside the positioner.
3.6
Health Data
View the warning level for each category. The 520MD+ 
positioner monitors the conditions that affect the ability of the 
valve to respond. As these conditions worsen, a warning 
level is shown. A low value such as 0% indicates no 
warning. A high value such as 90% indicates the ability to 
control may be impaired soon. A value of 100 indicates that 
the valve may no longer be responsive. 
3.6.1
Valve Health % Warning
The warning value from 0 to 100% based on warnings and 
alarms related to valve health such as friction. A lower value 
indicates less serious issues. 
3.6.2
Actuator Health % Warning
The warning value from 0 to 100% based on warnings and 
alarms related to actuator health such as supply pressure. A 
lower value indicates less serious issues. 
3.6.3
Positioner Health % Warning
The warning value from 0 to 100% based on warnings and 
alarms related to positioner health such as circuit board 
malfunction. A lower value indicates less serious issues. 
3.6.4
Control Health % Warning
The warning value from 0 to 100% based on warnings and 
alarms related to control health such as deviation. A lower 
value indicates less serious issues. 
3.7
Diagnostic Values
View basic diagnostic information. Pro diagnostics are 
required. 
3.7.1
Friction
View the friction of the valve and actuator assembly.
3.7.2
Actuation Ratio
View the effort required to move the valve in the direction that 
compresses the spring. The ratio is the force required to 
overcome friction, spring, and process load forces over the 
force available from the current supply pressure. 
3.7.3
Pneumatic Leak
View the pneumatic leakage of the actuator. This value does 
not include normal air consumption. 
3.7.4
Valve Travel
View the amount the valve has traveled in percent of total 
stroke length. 
3.7.5
Valve Cycles
View the number of cycles the valve has travelled. This is 
the number of times the valve has changed directions twice. 
3.7.6
Piezo Volts
View the voltage supplied to the piezo element in the 
positioner's pilot relay. This should typically be between 0 
and 24 VDC. 