16 main board status, 17 electronic board status, 18 stroke/friction status – Flowserve Logix 520MD+ DD User Manual
Page 23: 19 main board status, 20 electronic comp status, 21 software status, 22 press cal status, 10 calibrate mfc 2 analog out, Alibrate, Nalog
DD User Manual - Logix® 520MD+ Series Digital Positioner FCD-LGENSF0013-01
© Flowserve Corporation
23
8.9.16
Main Board Status
Select DO in slot 2 to trigger on Main Board Electronic
Failure Warning, Software Error Warning, Memory Error
Warning, Temperature High Warning, and Temperature Low
Warning.
8.9.17
Electronic Board Status
Select DO in slot 2 to trigger on Aux Card 1 Failure Warning,
Aux Card 2 Failure Warning, Aux Card 1 No Loop Power,
Aux Card 2 No Loop Power, Aux Card 1 Error, Aux Card 2
Error, Pressure Sensor Board Failure Warning, and Low
Battery Warning.
8.9.18
Stroke/Friction Status
Select DO in slot 2 to trigger on Reversed Spring, Insufficient
Spring, and No Spring.
8.9.19
Main Board Status
Select DO in slot 2 to trigger on Humidity Sensor Failure,
Oscillator Fault, Position Sensor ADC Failure, Supply
Voltage Error, Reference Voltage Error, Shunt Voltage Error,
and Piezo Voltage Error.
8.9.20
Electronic Comp Status
Select DO in slot 2 to trigger on Pilot Can't Open, Pilot Can't
Shut, Hall Sensor Failure, and ILO Out Of Range.
8.9.21
Software Status
Select DO in slot 2 to trigger on NVMEM CRC Error, RAM
Error, RAM CRC Error, FLASH CRC Error, Watch Dog Time
Out, Stack Overflow Warning, CPU Usage Warning, and
Firmware Update Applied.
8.9.22
Press Cal Status
Select DO in slot 2 to trigger on Port S Out Of Range, Port A
Out Of Range, Port B Out Of Range, Port S Range too
Small, Port A Range too Small, Port B Range too Small, and
Pressure Sensor Failure.
8.10 Calibrate MFC 2 Analog Out
If the card in slot 2 is an Analog Output, perform an analog
output calibration.