5 cst on/off, 6 calibration, 1 calibrate sensors – Flowserve Logix 520MD+ DD User Manual
Page 12: 2 calibrate command input, 3 calibration dates and times, 4 calibrate mfc analog out 1, 5 calibrate mfc analog out 2, 6 calibration status, 1 startup status, 2 calibration status

DD User Manual - Logix® 520MD+ Series Digital Positioner FCD-LGENSF0013-01
© Flowserve Corporation
12
 
 
View the number of times the valve failed to move at the end 
of a ramp. 
5.2.5
CST On/Off
Turn CST on or off. Warning: The CST will cause small 
periodic valve movements. 
 
 
6 CALIBRATION
Calibrate all aspects of the positioner.
6.1
Calibrate Sensors
Calibrate the stroke, pressure sensors, friction feature, or all 
of them in one operation using the "Triple" calibration. 
6.2
Calibrate Command Input
Calibrate the analog command input. Typically this will be 4 
to 20 mA. However, a split range can be set also. 
DANGER: Using this feature will result in valve movement
and the inability to operate the valve until the operation is 
complete. Notify proper personnel that the valve may 
stroke, and make sure the valve is properly isolated before 
proceeding. 
6.3
Calibration Dates and Times
View a history of previous calibration dates and times.
6.4
Calibrate MFC Analog Out 1
Calibrate the analog output. A multi-function card (MFC) 
must be installed in slot 1 and configured for the AO function. 
6.5
Calibrate MFC Analog Out 2
Calibrate the analog output. A multi-function card (MFC) 
must be installed in slot 2 and configured for the AO function. 
6.6
Calibration Status
 
View details about the calibration flags. 
 
6.6.1
StartUp Status
View the state of the positioner including Power ON, 
Initializing, Stroke Calibration Required, Pressure Calibration 
Required, and Friction Calibration Required. 
6.6.2
Calibration Status
View the state of the positioner including Stroke Calibration in 
Progress, Setting Inner Loop Offset, Pressure Calibration in 
Progress, Friction Calibration in Progress, Command Input 
Calibration in Progress, Analog Output Calibration In 
Progress, and Jog Calibration Set 100% Position. 