beautypg.com

Figure 3 - low voltage wiring connections 5 – First Co EVBQ (Variable Speed) User Manual

Page 5

background image

from unit (as measured along the low-voltage wires), use No. 16 AWG color-coded, insulated (35 degrees C minimum) wires.
Connect low-voltage thermostat leads and low-voltage outdoor unit leads to the fan coil circuit board as shown on unit
wiring diagram. (See Figure 3.)

CAUTION:

Do not use power stealing thermostats. The thermostat will cause the motor to function

improperly. A high grade digital thermostat is recommended. Failure to do so could result in damage to
components and will void all warranties.

Figure 3 - Low Voltage Wiring Connections

5

* NOTE - Some Thermostats may require a jumper between “E” and “W1”. Most Heat Pump
Thermostats have an “E” terminal for Emergency Heat. When the Tstat is switched from “Normal” to
“Emergency” the compressor circuit “Y” is locked out. Usually “E” becomes the 1st stage of heat. If
no heat call occurs on a temperature drop below set point, jumper “E” to “W” at the Tstat or at the
fan coil. If unit runs continuously on temperature rise above set point, remove jumper and refer to
the thermostat installation instructions.

Y1

W/W1

Y2

G

C

R

Y1

W1

Y2

G

C1

R

NC

HUM

Y1

Y2

R

C

DEHUM

Two Stage A/C Cooling

W/ Single Stage Heat

INDOOR

TSTAT

FAN COIL

24V

CONNECTIONS

2 STAGE

OUTDOOR

CONDENSER

Y

G

W

C

R

Y2

G

W1

C1

R

NC

HUM

Y

C

DEHUM

Single Stage A/C Cooling

W/ Single Stage Heat

INDOOR

TSTAT

FAN COIL

24V

CONNECTIONS

OUTDOOR

CONDENSER

Y

G

O/B

W

E

C

R

Y2

G

O

W1

EM

C1

R

NC

HUM

Y

O/B

W2

R

C

DEHUM

Single Stage Heat Pump

W/ Auxiliary / Backup Heat

INDOOR

TSTAT

FAN COIL

24V

CONNECTIONS

OUTDOOR

HEAT PUMP

O/B

Y1

W/W1

Y2

E

G

C

R

O

Y1

W1

Y2

EM

G

C1

R

NC

HUM

O/B

Y1

W

Y2

R

C

DEHUM

Two Stage Heat Pump

W/ Auxiliary / Backup & Emergency Heat

INDOOR

TSTAT

FAN COIL

24V

CONNECTIONS

OUTDOOR

HEAT PUMP

*

*