First Co FWA-HW User Manual
Fwa-aq series hot water furnace, Installation, operation & maintenance instructions
FWA-AQ SERIES
HOT WATER FURNACE
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
GENERAL
The manufacturer assumes no re-
sponsibility for equipment installed in
violation of any code requirement.
These instructions give information
relative to the installation of these fan
coil units only. For other related
equipment refer to the proper instruc-
tions.
Material in this shipment has been
inspected at the factory and released
to the transportation agency in good
condition. When received, a visual
inspection of all cartons should be
made immediately. Any evidence of
rough handling or apparent damage
should be noted on the delivery re-
ceipt and the material inspected in
the presence of the carrier’s repre-
sentative. If damage is found, a claim
should be filed against the carrier
immediately.
Note: State of MA.-248 CMR code of the
state of MA. requires a pump timer (60
seconds on every 6 hours). See dia-
gram.
FAN COIL UNIT
The installer must adhere strictly
to all local and national code require-
****** WARNING ******
Unit must not be operated
during building construction
due to excessive airborne dust
and debris. The unit must not
be operated under any
circumstances without an air
filter in place.
ments pertaining to the installation of
this equipment.
These units are designed to be
installed in either an upflow, downflow
or horizontal position.
All fan coil units are U.L. listed for
installation with zero inches clear-
ance to combustible materials. This
includes the unit cabinet, discharge
plenum and connecting ducts. Suffi-
cient clearance must be provided at
the front of the unit to allow access to
limit the unit to installation only in a
single story residence. In many
cases it is acceptable to use ducting
of the same size as the fan coil
connections. However, unique ar-
rangements or long duct runs must be
confirmed by a local professional.
The manufacturer will not be respon-
sible for misapplied equipment.
E
LECTRICAL
All wiring must comply with local
and national code requirements.
Units are provided with wiring dia-
grams and nameplate data to provide
information required for necessary
field wiring. Knockouts are provided
on each side of the cabinet for con-
nection of power supply.
These units may be provided with a
Class 2 transformer for 24-volt control
circuits. Should any add-on equip-
ment also have a Class 2 transformer
furnished, care must be taken to pre-
vent interconnecting outputs of the
two transformers by using a thermo-
stat with isolating contacts.
****** WARNING ******
Any devices such as fan
switches or thermostats that
have been furnished by the
factory for field installation
must be wired in strict accor-
dance with the wiring diagram
that is supplied with the unit.
Failure to do so could result
in damage to components
and will void all warranties.
L2462 02/09
****** WARNING ******
Extreme caution must be
taken that no internal damage
will result if screws or holes are
drilled into the cabinet.
electrical controls and removal of the
motor / blower assembly for servicing.
This clearance distance should be
approximately the same depth as the
fan coil unit.
AIR DISTRIBUTION
DUCTS
All duct work must be installed in
accordance with National Fire Protec-
tion Association Codes 90A and 90B.
Ducts should be adequately insulated
to minimize heat loss during the heat-
ing cycle. All return air must be filtered
to prevent dirt buildup on the coil sur-
face. If there is no ducted return,
applicable installation codes may
**WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER**
Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty
and may result in adverse operational performance and/or a possible hazardous safety condition to service
personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.
Current Maintenance Program is available at www.firstco.com under "Product Information".