The fan coil must be configured to operate properly with system components with which it is installed. To successfully
configure a basic system select the proper setting of the four Select Taps.

Cooling Select Tap –

Select system airflow for size of outdoor unit installed. See figure 10.

Refer to Table 1 to select the proper airflow and Select Tap for the system installed. Proper selection should be derived from
the outdoor unit capacity (tons) multiplied by nominal CFM per ton. (ex. 3 tons x 400 = 1200 CFM)

Heating Select Tap –

Select system airflow for heat output. See figure 10.

Refer to Table 1 to select the proper airflow and Select Tap for the hot water coil installed. Proper selection should be
derived from BTUH output of the coil from the unit specification sheet. The typical selection would be 350 to 400 CFM per
ton.

Adjust Select Tap –

Select system CFM airflow requirement. See figure 10.

Adjust select options are provided to adjust airflow supplied to meet individual installation conditions such as noise,
comfort and humidity removal. To provide airflow at rates described in Table 1, the Adjust Tap is factory set at nominal
(NORM). The adjust selections will regulate airflow supplied for all operational modes. The (+) tap provides 10 percent
airflow over nominal airflow selected and the (-) tap provides 10 percent airflow below nominal airflow selected.

Delay Select Tap –

Select desired delay profiles. See figure 10.

Four operation delay profiles are provided to customize and enhance system operation.

NOTE:

The delay profiles are active only in the cooling modes.

C1 R HUM

HEAT

A
B
C
D

COOL

A
B
C
D

D

TEST

DEHUMIDIFY

CUT TO ENABLE

Figure 9 - Dehumidify Resistor on Select Control Board

CUT RESISTOR TO

ACTIVATE

DEHUMIDISTAT

Selection Options:

A – Arid Climates – the motor is programmed with a minimum ramp time to achieve full cooling capacity within a short

time period. The off cycle delay is programmed with a reduced airflow over an extended time period.

B - Mild Humid Climates – the motor is programmed with ramp time and speed to achieve dehumidification on cooling

start-up, thus allowing more moisture to collect and drain from the coil. The off cycle delay is programmed with a
reduced airflow and short time period to enhance system efficiency and minimize re-evaporation of condensate.

C - Humid Climates – the motor is programmed with extended ramp time and reduced speed to achieve maximum

dehumidification on cooling start-up, thus allowing more moisture to collect and drain from the coil. There is no
off cycle delay programmed to eliminate re-evaporation of condensate.

D – No Delays – the motor is programmed with no delays to represent normal operation of a standard air handler.

Heat Delay -

the motor is factory programmed with a pre-purge time to permit the circulator to circulate hot water to the fan

coil before the blower operates at a reduced CFM. The off cycle delay is programmed with a reduced airflow over a short
time period to post purge the heat out of the water coil and duct system.

NOTE: The unit does NOT read changes in COOL, HEAT, and DELAY taps while it is running. Disconnect power
for 1 minute before changing taps, then restart for the new settings to take affect.