Heating mode – If the indoor temperature is below the thermostat set point, the thermostat sends a signal to the fan coil
to deliver heat pump and hot water heating airflow.
Emergency Heat – If the thermostat is set to emergency heat, the thermostat sends a signal to deliver hot water heat
only. No mechanical heat is produced from the heat pump.
NOTE:
Some thermostats may require a jumper between Emergency heat and W1 for proper operation.
Refer to the thermostat installation instructions for more information.
1
4
5
3
2
AC
LINE
AC
LINE
CHASSIS
GROUND
JUMPER PIN 1 TO PIN 2 FOR
120VAC LINE INPUT ONLY
Figure 11 - 5 Pin Power Connector
Table 2 - Wiring Harness Terminations
* Check voltages wit 16-Pin Plug disconnected from the motor.
** These signals will start the motor.
Dehumidify - 24VAC is present with a call for no dehumidication.
Figure 10 - 16 Pin Signal Connector
WARNING:
Applying 240VAC line input
with Pin 1 and Pin 2 jumper in place
will permanently damage unit.
14
Pin # on
16-Pin
Connector
Signal on pin with
Screw Terminal
Jumpered to R *
1
Common
2
W /W1
Heating Signal
24VAC **
3
Common
4
Delay Adjust
5
Cool Fan Adjust
6
Y1
AC / Heat Pump
(-) 12VDC **
7
CFM Adjust
8
Not Used
9
"O" (HP/Cool)
Reversing Valve
10
Dehumidify
0V (24VAC on no call)
11
Heat Fan Adjust
12
24V AC
24VAC continuous
13
W2 / EM
Heating Signal
24VAC **
14
Y /Y2
AC / Heat Pump
(-) 12VDC **
15
G
Fan Signal
24VAC **
16
Not Used
Description
16-Pin Motor Wiring Harness to 16-Pin Connector on Select Board
1
2
3
4
6
5
7
8
9
10
11
12
14 13
15
16
G
24v
DH
C W1 C
Y2