Heating mode – If the indoor temperature is below the thermostat set point, the thermostat sends a signal to the fan coil
to deliver heat pump and hot water heating airflow.

Emergency Heat – If the thermostat is set to emergency heat, the thermostat sends a signal to deliver hot water heat

only. No mechanical heat is produced from the heat pump.

NOTE:

Some thermostats may require a jumper between Emergency heat and W1 for proper operation.

Refer to the thermostat installation instructions for more information.

1

4

5

3

2

AC

LINE

AC

LINE

CHASSIS

GROUND

JUMPER PIN 1 TO PIN 2 FOR

120VAC LINE INPUT ONLY

Figure 11 - 5 Pin Power Connector

Table 2 - Wiring Harness Terminations

* Check voltages wit 16-Pin Plug disconnected from the motor.
** These signals will start the motor.
Dehumidify - 24VAC is present with a call for no dehumidication.

Figure 10 - 16 Pin Signal Connector

WARNING:

Applying 240VAC line input

with Pin 1 and Pin 2 jumper in place
will permanently damage unit.

14

Pin # on

16-Pin

Connector

Signal on pin with

Screw Terminal

Jumpered to R *

1

Common

2

W /W1

Heating Signal

24VAC **

3

Common

4

Delay Adjust

5

Cool Fan Adjust

6

Y1

AC / Heat Pump

(-) 12VDC **

7

CFM Adjust

8

Not Used

9

"O" (HP/Cool)

Reversing Valve

10

Dehumidify

0V (24VAC on no call)

11

Heat Fan Adjust

12

24V AC

24VAC continuous

13

W2 / EM

Heating Signal

24VAC **

14

Y /Y2

AC / Heat Pump

(-) 12VDC **

15

G

Fan Signal

24VAC **

16

Not Used

Description

16-Pin Motor Wiring Harness to 16-Pin Connector on Select Board

1

2

3

4

6

5

7

8

9

10

11

12

14 13

15

16

G

24v

DH

C W1 C

Y2