First Co SPXA (cooling with electric heat) User Manual
Spu series, Wall sleeve, Installation instructions
WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER
Altering the product or replacing parts with non authorized factory parts voids all warranty or
implied warranty and may result in adverse operational performance and/or a possible hazardous safety
condition to service personnel and occupants. Company employees and/or contractors are not autho-
rized to waive this warning.
GENERAL
These instructions give information
relative to the SPU series wall sleeve and
grille installation only. The manufacturer
assumes no responsibility for equipment
installed in violation of any code require-
ments. For other related equipment refer
to the proper instructions.
The grille and wall sleeve are shipped
in separate packages. Material in this
shipment has been inspected at the factory
and released to the transportation agency
in good condition. When received, a visual
inspection of all cartons should be made
immediately. Any evidence of rough
handling or apparent damage should be
noted on the delivery receipt and the
material should be inspected in the
presence of the carriers representative.
If damage is found a claim should be filed
against the carrier immediately.
DESCRIPTION
The SPU wall sleeve is designed to pro-
vide the structural support and seal from
the outside elements for the SPU pack-
age system. There is no need to build a
platform base for the SPU. The base of
the sleeve also acts as the drain pan for
the system. A 3/4 NPT nipple is located in
the bottom of the pan to be connected to
the condensate drain plumbing.
LOCATION
The SPU unit is designed for through
the wall installation in a closet with direct
access to the rear of the unit (Fig. 1). The
exterior (grille side) of the unit must have
no obstructions (trees, landscape
materials, or building structure, etc.) within
18 inches. Do not locate two units
adjacent to each other on an inside corner
or anyplace where they may exhaust into
each other.
Provisions should be made to allow for
access to the indoor (rear) side of the unit
for installation and inspection. The closet
door must be centered with the exterior
wall opening and be at least 24 wide by
84 tall. At least three (3) inches of space
is required on the left and right sides of
the sleeve and 8-1/2 inches of space is
required from the rear of the sleeve to pro-
vide sufficient air flow around the SPU unit.
A minimum of 27 inches of unobstructed
space should be provided in front of the
access door to permit removal of the unit
should repair and inspection be required.
WALL SLEEVE
INSTALLATION
1. The wall sleeve is supplied with a
weather guard to protect against the
elements prior to the installation of
the grille.
2. A construction debris guard is
supplied to protect the lower seals
and drain from damage or clogging
caused by construction.
3. The wall sleeve is supplied with a 3/
4 NPT pipe nipple for connection to
condensate drain plumbing.
SPU SERIES
WALL SLEEVE
INSTALLATION INSTRUCTIONS
4. Install the sleeve into a pre-cut
opening 44H x 21-5/8W. Use shims
as necessary to maintain proper
alignment of the sealing surfaces.
Sleeve sides must remain in contact
with the seal frame and parallel with
each other or air leakage will occur.
Note: The factory applies a sealant to
the outside of the interface between
the seal and the sleeve. The installer
is responsible to check this for
damage due to installation and to add
sealant as necessary to ensure that
no air gaps exist.
OUTSIDE
WALL
Centerline of Closet
and Exterior Opening
SPU Unit
Wall Sleeve
Figure 1
L2631 2/04
********* Warning**********
After sleeve installation ensure
that the sleeve seal is in contact
with the sleeve sides. Any air
gaps must be sealed or outdoor
air and/or water leakage will
occur.