WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER

Altering the product or replacing parts with non authorized factory parts voids all warranty or

implied warranty and may result in adverse operational performance and/or a possible hazardous safety

condition to service personnel and occupants. Company employees and/or contractors are not autho-

rized to waive this warning.

GENERAL

These instructions give information

relative to the SPU series wall sleeve and

grille installation only. The manufacturer

assumes no responsibility for equipment

installed in violation of any code require-

ments. For other related equipment refer

to the proper instructions.

The grille and wall sleeve are shipped

in separate packages. Material in this

shipment has been inspected at the factory

and released to the transportation agency

in good condition. When received, a visual

inspection of all cartons should be made

immediately. Any evidence of rough

handling or apparent damage should be

noted on the delivery receipt and the

material should be inspected in the

presence of the carrier’s representative.

If damage is found a claim should be filed

against the carrier immediately.

DESCRIPTION

The SPU wall sleeve is designed to pro-

vide the structural support and seal from

the outside elements for the SPU pack-

age system. There is no need to build a

platform base for the SPU. The base of

the sleeve also acts as the drain pan for

the system. A 3/4 NPT nipple is located in

the bottom of the pan to be connected to

the condensate drain plumbing.

LOCATION

The SPU unit is designed for through

the wall installation in a closet with direct

access to the rear of the unit (Fig. 1). The

exterior (grille side) of the unit must have

no obstructions (trees, landscape

materials, or building structure, etc.) within

18 inches. Do not locate two units

adjacent to each other on an inside corner

or anyplace where they may exhaust into

each other.

Provisions should be made to allow for

access to the indoor (rear) side of the unit

for installation and inspection. The closet

door must be centered with the exterior

wall opening and be at least 24” wide by

84” tall. At least three (3) inches of space

is required on the left and right sides of

the sleeve and 8-1/2 inches of space is

required from the rear of the sleeve to pro-

vide sufficient air flow around the SPU unit.

A minimum of 27 inches of unobstructed

space should be provided in front of the

access door to permit removal of the unit

should repair and inspection be required.

WALL SLEEVE

INSTALLATION

1. The wall sleeve is supplied with a

weather guard to protect against the

elements prior to the installation of

the grille.

2. A construction debris guard is

supplied to protect the lower seals

and drain from damage or clogging

caused by construction.

3. The wall sleeve is supplied with a 3/

4” NPT pipe nipple for connection to

condensate drain plumbing.

SPU SERIES

WALL SLEEVE

INSTALLATION INSTRUCTIONS

4. Install the sleeve into a pre-cut

opening 44”H x 21-5/8”W. Use shims

as necessary to maintain proper

alignment of the sealing surfaces.

Sleeve sides must remain in contact

with the seal frame and parallel with

each other or air leakage will occur.

Note: The factory applies a sealant to

the outside of the interface between

the seal and the sleeve. The installer

is responsible to check this for

damage due to installation and to add

sealant as necessary to ensure that

no air gaps exist.

OUTSIDE

WALL

Centerline of Closet

and Exterior Opening

SPU Unit

Wall Sleeve

Figure 1

L2631 2/04

********* Warning**********

After sleeve installation ensure

that the sleeve seal is in contact

with the sleeve sides. Any air

gaps must be sealed or outdoor

air and/or water leakage will

occur.