INSTALLATION REQUIREMENTS

Installation must be performed by a qualifi ed professional service
technician.

This grill is designed for outdoor use only. DO NOT use this grill inside
a building, garage, enclosed area, or under an unprotected overhead
combustible construction.

See below and the EXHAUST REMOVAL section on the following
page for details on installing under overhead construction.

DO NOT use this grill in or on a recreational vehicle or boat.

Important: If installing this grill in a combustible surround, the correct

RHP insulating liner must be used.

Important: Refer to the information below to ensure all required

clearances are met.

The grill must have a minimum clearance of 18" from combustible
materials/items
AT ALL TIMES.

Overhead Construction Requirements (if applicable)

Non-combustible overhead construction: A 6 foot clearance is required
between the countertop and the construction above (Fig. 11-1).

Combustible overhead construction: A 6 foot clearance is required
between the countertop and the construction above. A vent hood
(see EXHAUST REMOVAL section) or an RHP combustible overhead
protection kit is required directly above the grill. See Fig. 11-1. RHP
vent hoods and protection kits are available, contact your local
dealer
.

Side and Rear Wall Clearances

For the minimum clearances between the grill and any side or rear
walls, your setup must fall within one (or more) of the following:

A. Clearance between grill and strictly non-combustible wall

(i.e. brick wall, see Fig. 11-2)

• The grill must have a minimum of 4" right, left, and rear

clearance from any non-combustible wall.
(To allow for proper ventilation and prevent dangerous
overheating.)

B. Clearance between grill and a protected combustible wall

(i.e. a non-combustible wall in front of a combustible wall to serve
as a barrier. This can be accomplished by brick, or a metal stud
fi nished with non-combustible substrate, see Fig. 11-3)

• The grill must have a minimum of 14" right, left, and rear

clearance from the protected combustible wall.
(The 4" non-combustible material plus an additional 10"
clearance between the grill and protected wall.)

C. Clearance between grill and combustible wall

• The grill must have a minimum of 18" right, left, and rear

clearance from any combustible wall (see Fig. 11-4).

Backsplash Clearance (if applicable)

If a non-combustible backsplash exists, it must have a minimum of a
4" clearance from the rear of the grill (to allow for proper ventilation
and prevent dangerous overheating). See Fig. 11-5.

Important: This 4" backsplash clearance must fi rst be met prior to

any non-combustible walls beginning behind it.

Fig. 11-2 Clearance 'A' Diagram

Fig. 11-3 Clearance 'B' Diagram

Fig. 11-4 Clearance 'C' Diagram

Non-combustible

Min.

4"

Min.

14"

Non-combustible

substrate

Non-combustible 4"

Combustible

Min.

18"

(Clearance required for

right, left, and rear)

Fig. 11-5 Backsplash clearance

Non-combustible

Backsplash

Min.

4"

Com-

bustible

(Clearance required for

right, left, and rear)

(Clearance required for

right, left, and rear)

Fig. 11-1 Overhead requirements

Min.

6'

Combustible construction:

Requires vent hood or protection kit

Non-combustible construction:

Okay as-is

REV 5 - 1412081445