FIREPLACE INSTALLATION

Continued

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1.

Open lower louver door panel by gently pulling forward.

2.

Route flexible gas line (provided by installer) from equipment
shutoff valve to fireplace. Route flexible gas supply line through
one of the access holes on side of fireplace.

3.

Attach flexible gas line from gas supply to control valve (see
Figure 32).

4.

Check all gas connections for leaks. See Checking Gas Connections.

FIREPLACE INSTALLATION

Connecting Fireplace To Gas Supply
Checking Gas Connections

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect fireplace and its individual equipment shutoff valve
from gas supply piping system. Pressures in excess of 1/2 psig
(3.5 kPa) will damage fireplace gas regulator.

2.

Cap off open end of gas pipe where equipment shutoff valve
was connected.

3.

Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas fireplace or opening main
gas valve located on or near gas meter for natural gas fire-
place, or using compressed air.

4.

Check all joints of gas supply piping system. Apply noncorro-
sive leak detection fluid to all joints. Bubbles forming show a
leak. Correct all leaks at once.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections,

internal and external to unit, for leaks after installing
or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for

a leak. Apply a noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak. Correct all leaks
at once.

5.

Reconnect fireplace and equipment shutoff valve to gas sup-
ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Figure 33).

2.

Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas fireplace or opening main
gas valve located on or near gas meter for natural gas fire-
place, or using compressed air.

3.

Check all joints from propane/LP supply tank or gas meter to
equipment shutoff valve (see Figure 34 for propane/LP or Figure
35 for natural gas). Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak. Correct all leaks at once.

Figure 33 - Equipment Shutoff Valve

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Propane/LP
Supply Tank

Gas Valve

Equipment
Shutoff
Valve

Gas
Meter

Gas Valve

Equipment
Shutoff
Valve

Figure 32 - Connecting Flexible Gas Line to Electronic Valve

1/2" NPT Incoming
Gas Line

Inlet Pressure Tap

Outlet Pressure Tap

Equipment
Shutoff Valve

Flexible Gas Line
Do NOT Kink

Note: Wire Connections Not Shown for Clarity

Red Surface Indicates
For Propane/LP Use Only

Open

Closed

Equipment
Shutoff
Valve