beautypg.com

Installation, En l1 l2 l3 – DC Power Technologies FS5 - Owners Manual User Manual

Page 5

background image

5

Installation

Location
The recommended installation is where the charger(s) can be located
at ground level or on a raised platform, protected against accidental
contact with the lift truck or its forks. Installation above ground level is
recommended to reduce the level of dust ingested by the charger.

AC Input
The FS5 and FS9 chargers require 480V, 3 phase AC supply. Care must be
taken to install your charger with the appropriate rated AC supply cable.

FS5: 6 AWG Copper Conductors

FS9: 6 AWG Copper Conductors, rated 167°F / 75°C minimum

Refer to the rating label on your charger for AC supply requirements
specific to your configuration.

AC Supply Wiring Configuration

E

N

L1

L2

L3

L1

L2

L3

480V AC

Delta

Earth

Note: It is common in the US that a fourth wire (neutral) be used in a

triple phase circuit. If present, it should be attached to the “E” terminal.

This manual is related to the following products: