Configuration Settings
Charge Profiles Available:
Conventional Charge IUIa/IEI
Opportunity Charge
Fast Charge (battery module required)
Battery Types:
Flooded, Sealed, Gel.
Environments:
Standard, Freeze/cold condition.
Cable Length:
Combined charger and battery cable length in metres.
Equalize Charge Settings:
Cycle count:
Adjustable to any number. Default setting is to equalize
charge after every 5 complete charge cycles.
Day/time:
Select day and time of the week to trigger an equalize charge
on the next charge cycle. Can also select to have it equalize
charge every other week.
Manual equalize: Select to have an equalize charge run from the display panel.
Contact your local Eco Charge / Dealer for assistance with the adjustment
of these settings.
Ampere-Hour Ranges:
FS5
FS9
Low limit (Ahr)
Upper Limit (Ahr)
Low limit (Ahr)
Upper Limit (Ahr)
Conventional Profile (16A/100Ahr)
24V
300
1875
300
3375
36V
300
1875
300
3375
48V
300
1575
300
2810
Opportunity Profile (25A/100Ahr)
24V
300
1200
300
2160
36V
300
1200
300
2160
48V
300
1000
300
1800
Fast Profile (40A/100Ahr)
24V
300
750
300
1350
36V
300
750
300
1350
48V
300
625
300
1125