Termination, Bias – Contemporary Control Systems AI-SRVR Servers to Ethernet Installation Guide User Manual
Page 9

TD000200-0IH
9
Termination
Each end of a segment must be terminated in the characteristic
impedance of the cable. A 120-ohm internal resistance can be invoked
with a jumper on the EIA-485 daughter board. With the middle jumper
inserted at E1 on the daughter board, 120 ohms of resistance is applied
across the twisted-pair. With the jumper removed, no termination is
applied. To apply external termination instead, remove this jumper and
install a 120-ohm ¼ watt resistor across pins A and B of the screw
terminal connector. A resistance value under 120 ohms is not
recommended since it may excessively load the EIA-485 transceivers.
Bias
In addition to termination, bias must be applied to the ends of a twisted-pair
network (and nowhere else) so that when the line is floated, differential
receivers will not assume an invalid logic state. There are two precision bias
resistors (Rb) of equal value on the daughter board, one tied to +5 V and the
other to ground. Each resistor has a jumper associated with it. If both
jumpers are installed, the resistor tied to +5 V is connected to the (+) signal
and the grounded resistor is connected to the (–) line.
The termination and bias rules are simple. If the AI-SRVR/485 is at the end
of the segment, install all three jumpers at location E1 on the daughterboard.
Otherwise, remove all three jumpers. To use external termination, removed
the middle jumper at E1.
For EIA-485 DC operation, it is very important that all devices on the
segment be referenced to the same ground potential so that the common
mode voltage requirement (+/–7 Vdc) of the EIA-485 specification is
achieved. This can be accomplished by a separate ground wire tied to all
devices or using the third wire ground of the power connector. Alternately,
connect the DC common of each node to a cold water pipe. Connected
systems having different grounds, can cause unreliable communications
or can damage the drivers. Therefore, adequate grounding must be
implemented. A ground connection can be found at pin 3 of the screw
terminal connector.