Specifications, Connector information – Contemporary Control Systems AI-SRVR Servers to Ethernet Installation Guide User Manual
Page 3
![background image](https://www.manualsdir.com/files/779037/content/doc003.png)
TD000200-0IH
3
ARCNET Data Rates
SpECIFICATIONS
Electrical
INpUT
DC
AC
Voltage:
10–36 V 8–24 V
Power (max): 8 W
8 VA
Frequency: N/A
47–63 Hz
Ethernet Data Rates
10/100 Mbps
LED Indicators
Status—green
ARCNET
Ethernet
RX—green
LINK/ACT— green/yellow
ACT—yellow DUP— green/yellow
Environmental
Operating temperature: 0°C to +60°C
Storage temperature: –40°C to +85°C
Humidity, non-cond.:
10% to 95%
Regulatory Compliance
CE Mark, RoHS
CFR 47, Part 15 Class A
UL 508 Listed
(intended for use with Class 2 circuits only)
Compatibility
ANSI/ATA 878.1 and IEEE 802.3
Shipping Weight
1 lb. (.45 kg)
Ethernet Socket Pins (RJ-45)
pIN USAGE
1
TD+
2
TD–
3
RD+
6
RD–
(All other pins are unused.)
ARCNET Socket Pins (RJ-45)
4 Line – (Phase B)
5 Line + (Phase A)
(all other pins are unused)
Figure 1 — RJ-45 Connector
CONNECTOR INFORmATION
ARCNET Socket Pins (3-pin screw connector)
485
485X
SH Shield
Shield
B Line –
Line
A Line + Line
Console Port EIA-232 Pins (DE-9 connector)
pIN Signal Function
2
RXD Receive Data
3
TXD Transmit Data
5
GND Ground
(all other pins are unused)
Console Port EIA-232 (DE-9)
Communication Parameters
Baud Rate
57,600 bps
Data Bits
8
Parity
No Parity
Stop Bit
1
Figure 2 —
3-pin Connector
Figure 3 —
DE-9 Connector