beautypg.com

2 field bus installation, 1 general, 2 profibus connector – Bronkhorst PROFIBUS-DP slave interface User Manual

Page 8: 2field bus installation, 2 profibus

background image

BRONKHORST

®

2

FIELD BUS INSTALLATION

2.1

G

ENERAL

The following installation guidelines only apply to data transfer using copper cables (RS 485) to EN

50170. Furthermore, operators of PROFIBUS equipment are strongly recommended only to use field bus

devices and components which have been certified by the PROFIBUS User Organization e.V. (PNO).

Certified products have undergone extensive tests carried out by specialists to demonstrate their

compliance to the PROFIBUS standard EN 50170 in combination with PROFIBUS devices from other

manufacturers. PROFIBUS data transfer is based on the RS 485 standard

1

. The relevant features for use

with PROFIBUS-DP are described in EN 50170.

PROFIBUS DP field bus wiring is the cause of many problems if not proper installed.

Please use the instructions below and those mentioned on

www.profibus.com

2.2

PROFIBUS

CONNECTOR

The chassis female PROFIBUS DP (sub miniature 9-pin) D-connector has the following pin configuration:

Pin number

Description

1

not connected

2

not connected

3

RxD/TxD-P

-

plus (B – wire)

4

RTS

5

DGnd

6

VP(+5V)

7

not connected

8

RxD/TxD-N

-

minus (A - wire)

9

not connected

The chassis female PROFIBUS M12 B-coded connector (IP65) has the following pin configuration:

Pin number

Signal

Description

1

VP

Power supply plus, (P5V)

2

RxD / TxD-N

Receive / Transmit data –N, A-line

3

DGND

Data ground (reference potential to VP)

4

RxD / TxD-P

Receive / Transmit data –plus, B-line

5

not connected

Thread

Shield

Shield or PE

Page 8

PROFIBUS DP interface

9.17.025