2 troubleshooting hints and tips – Bronkhorst PROFIBUS-DP slave interface User Manual

Page 24

background image

BRONKHORST

®

8.2

T

ROUBLESHOOTING HINTS AND TIPS

PROFIBUS problems

No Communication

Check power supply and cabling.

Check bus termination. At the beginning and end of a bus segment, termination

should be enabled in your connector or by means of any external special resistor

network.

Check all PROFIBUS settings at your master. Master and slave settings for use of

memory modules must be the same. Select at least one module e.g. ‘Measure,

integer (read)’ otherwise there will be no data-exchange.

Check address of interface (slave)

Try to reset the instrument and/or restart your master.

Make sure all settings for your slave are downloaded to your master (otherwise it

won’t work).

Contact PROFIBUS sales representative or service department.

Flow is not reacting to

setpoint commands

In case of PROFIBUS communication problems instrument will put it’s valve into a

safe state. This will close (NC) or open the valve fully (NO). When data exchange

between master and slave has been re-established, instrument will respond to

setpoint again. For overruling safe state via RS232 interface, see setpoint /control

modes in chapter 2.5 from doc. nr. 9.17.023, (digital instrument description).

Red Led has long flash

Make sure the requested parameters are available in the particular Bronkhorst

Profibus-DP slave.

Delete the Profibus slave configuration and add a new slave in your software, this

will remove a corruption in the software configuration.