beautypg.com

2 maintenance, Quick check” inspections, Use and maintenance – Belshaw Adamatic INSIDER Ventless Donut System User Manual

Page 32: Fire suppression system

background image

Belshaw Bros., Inc.

• www.belshaw.com • Phone 206-322-5474 • Fax 206-322-5425

6 MN-1853EN

Insider

TS

2 Maintenance

“Quick Check” Inspections

Inspection shall be conducted on a monthly
basis
by the owner, in accordance with the
manufacturer’s installation and maintenance
manual. As a minimum, the “quick check” or
inspection shall include verification of the
following:
The fire suppression system is in its proper
location.
The manual actuators are unobstructed.
The maintenance tag or certification is in place.
No obvious physical damage or condition exists
that might prevent operation.
The pressure gauge is in operable range.
The nozzle blowoff caps are intact and
undamaged.
The hood, duct, and protected cooking
appliances have not been replaced, modified, or
relocated.
If any deficiencies are found, appropriate
corrective action shall be taken immediately.
Personnel making inspections shall keep records
for those fire suppression system that was found
to require corrective actions.
At least monthly, the date the inspection is
performed and the initials of the person
performing the inspection shall be recorded.
The records shall be retained for the period
between the semiannual maintenance
inspections.

Use and Maintenance

All filters shall be cleaned or replaced in
accordance with the manufacturer’s instructions.
The grease filter and pre-filter should be cleaned

daily. The carbon filters should be replaced a
minimum of every six (6) months.
The air cleaner cell shall be cleaned a minimum
of once per week following manufacturers
cleaning instructions.
The entire hood plenum and the blower section
shall be cleaned a minimum of once every three
(3) months.

Inspection and testing of the total operation and
all safety interlocks in accordance with the
manufacturers instructions shall be performed by
qualified service personnel a minimum of once
every six (6) months
or more frequently if
required.
A signed and dated log of maintenance as
performed in accordance with above shall be
available on the premises for use by the authority
having jurisdiction.

Fire Suppression System

WARNING

THE CHARGING & SETUP OF THE PYRO-

CHEM PLC-240/300 FIRE SUPPRESSION

SYSTEM MUST BE DONE BY CERTIFIED

PERSONNEL ON A REGULAR BASIS

AND THE USE AND MAINTAINENCE OF

THE INSIDER IS TO BE IN ACCORDANCE

WITH NFPA-96.

Fusible links and nozzle caps must be replaced at
least annually or more frequently if necessary to
ensure proper operation of the system. Fusible
links and all other detection devices must be
serviced or replaced in accordance with the
manufacturer’s recommendations.