2 status word (zsw), 2 operating modes, Operating modes – BECKHOFF AX2000 PROFIBUS DP communication profile User Manual
Page 37: Status word, Status word (zsw), Process data channel

5.1.2
Status word (ZSW)
With the help of the status word, the amplifier state can be represented and a transmitted control
word can be verified.
If the amplifier does not react to changes of the control word (STW) as expected, the marginal con-
ditions like (enable of the output stage – hardware + software, application of the DC bus link vol-
tage) must be checked.
The bits in the status word can be mode-dependent or mode-independent.
The following table describes the bit assignment in the status word.
Bit
Name
Commentary
0
Ready for switch-on
---
1
Switched on
---
2
Operation enabled
---
3
Error
see ASCII command ERRCODE
4
Voltage inhibited
---
5
Fast stop
---
6
Switch-on inhibit
---
7
Warning
see ASCII command STATCODE
8
Setpoint / actual value monitoring
only in position-control opmode: following error indicator
9
Remote
not supported, fixed to 1
10
Setpoint reached
only in position mode: In Position
11
Limit active
not supported at present
12
Depends on mode
used in ASCII-mode
13
Depends on mode
used in ASCII-mode
14
Manufacturer-specific
used in ASCII-mode
15
Manufacturer-specific
reserved
States of the status machine:
State
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Not ready for
switch-on
0
X
X
0
0
0
0
Switch-on inhibit
1
X
X
0
0
0
0
Ready for switch-on
0
1
X
0
0
0
1
Ready for operation
0
1
X
0
0
1
1
Operation enabled
0
1
X
0
1
1
1
Error
0
X
X
1
X
X
X
Error response
0
X
X
1
0
0
0
Fast stop active
0
0
X
0
1
1
1
5.2
Operating modes
The selection of a new operating mode is described in detail on p. 23. This procedure must be follo-
wed for proper amplifier operation.
WARNING
Appropriate precautionary measures against damage caused by faulty presentation of data
formats or normalization of the setpoints must be taken by the user.
The possible operating modes are described below. PROFIBUS operating modes with a positive
number (1,2) are defined in the drive profile. Operating modes with a negative number (-1,-2...) are
labeled in the drive profile as being manufacturer-specific modes.
PROFIBUS for AX2000/2500
37
BECKHOFF
12/05
Process data channel