Analog Output Point Object
23
IPxxxx-B520
7 Analog Output Point Object
Analog Output Points
The Analog Output Point Class allows the access to the IO-Data and the
Register Data of each analog output channel of the IPxxxx. At Boot Up the
IPxxxx determines the number of analog output channels and creates one
instance of the object class for each channel.
Class Code:
11 (0Bhex)
Class Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Description
Semantics of
Value
1
get
Revision
UINT
Revision of implementation
1
2
get
Max. Instance
UINT
Max. number of instances
Instance Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Description
Semantics of Value
3
(03hex)
Get/set Value
INT
or
based
on
Attribute 8
Value of analog output Number of Bytes
differs between ana-
log and special signal
boxes
4
(04hex)
Get
Status
BOOL
Indicates fault or alarm
conditions
0 = OK,
1 = alarm or fault
see semantics
7
(07hex)
Get
Output Range
USINT
Output Range
0 = 4mA to 20mA
1 = 0V to 10V
2 = 0mA to 20mA
3 = -100V to 10V
100 = Vendor Spec.
101 = Resistor
102 = Thermo
103 = SSI
104 = Increment
105 = Serial
8
(08hex)
Get
Value
Data
Type
USINT
Data type of Value
0 = INT
6 = UINT
100 = Vendor specific
9
(09hex)
Get
Fault State
BOOL
Output Value if failure
occurs
See semantics
10
(0Ahex)
Get
Idle State
BOOL
Output Value if idle
mode
See semantics