Register description

KL6051

9

Type registers

R8 - R15 Registers in the terminal’s internal ROM der Klemme
The type and system parameters are programmed permanently by the
manufacturer and can only be read by the user but cannot be modified.

R8: Terminal type:
The terminal type in register R8 is needed to identify the terminal.

R9: Software version X.y
The software version can be read as an ASCII character string.

R10: Data length
R10 contains the number of multiplexed shift registers and their length in
bits.
The bus coupler sees this structure.

R11: Signal channels
In comparison with R10, the number of logically existing channels is loca-
ted here. For example, one physically existing shift register may consist of
several signal channels.

R12: Minimum data length
The respective byte contains the minimum data length of a channel to be
transferred. If the MSB is set, then the control/status byte is not necessarily
needed for the function of the terminal and, with appropriate configuration
of the coupler, is not transferred to the control system.

R13: Data type register

Data type register

0x00

Terminal without valid data type

0x01

Byte array

0x02

1 byte n bytes structure

0x03

Word array

0x04

1 byte n words structure

0x05

Double word array

0x06

1 byte n double words structure

0x07

1 byte 1 double word structure

0x08

1 byte 1 double word structure

0x11

Byte-array with a variable logical channel length

0x12

1 byte n bytes structure with a variable logical channel
length (eg 60xx)

0x13

Word-array with a variable logical channel length

0x14

1 byte n words structure with a variable logical channel
length

0x15

Double word array with a variable logical channel length

0x16

1 byte n double words structure with a variable logical
channel length


R14: not used

R15: Alignment bits (RAM)
The analog terminal is set to a byte limit in the terminal bus with the align-
ment bits.

Manufacturer parameters

R16 - R30 is the area of the "Manufacturer parameters" (SEEROM)
The manufacturer parameters are specific to each terminal type. They are
programmed by the manufacturer but can also be modified from the control
system. The manufacturer parameters are stored permanently in a serial
EEPROM and are therefore not destroyed by power failures.
These registers can only be modified after setting a code word in R31.