2 technical data – BECKHOFF KL2502 User Manual
Page 7

Product
overview
KL2502, KL2512
5
2.2 Technical data
Technical data
KL2502
KL2512
Number of outputs
2
Rated load voltage
24 V
DC
(20 V ... 29 V)
switched potential
24 V
0 V
Load type
resistive, inductive
resistive
Max. output current (per channel)
0.1 A (short-circuit-proof)
1,0 A
Fundamental frequency
1 ... 20 kHz, 250 Hz default
Keying ratio
0 ... 100%
(T
on
> 750 ns, T
off
>500 ns)
0 ... 100%
Resolution
max. 10 bits
Electrical isolation
500 V
rms
(K-Bus / field voltage)
Current consumption from K-Bus
18 mA typ.
Leakage current
10 mA typ.
Bit width in the process image
48 I/O: 2 x 16 bits data, 2 x 8 bits control/status
Configuration
no address settings, configurations via bus coupler or control
system
Weight approx.
50 g
during operation
0°C ... +55°C
Permissible ambient
temperature range
during storage
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration/Shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29
EMC resistance Burst / ESD
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
any
Type of protection
IP20