11 rs422/rs485 connections (cx9020-n031) – BECKHOFF CX9020 User Manual
Page 29
Mounting and wiring
3.11
RS422/RS485 connections (CX9020N031)
The CX9020N030 system interface provides an RS422 or RS 485 interface, COM1 (X300). It is
implemented on a 9pole SubD socket strip. If more than one interface is required the system can be
extended via the Terminal Bus (K or Ebus) or Bus Terminals (KL/EL6021) which provide serial interfaces.
The pin assignment is shown at the bottom of the page.
The maximum baud rate on both channels is 115 kbit. The interface parameters are set via the operating
system or from the PLC program.
COM interface (socket)
Table 5: Pin assignment of the COM interface
PIN
Signal
Type
Description
2
TxD+
DataOut +
Transmit 422
3
RxD+
DataIn +
Receive 422
5
GND
Ground
Ground
6
VCC
VCC
+5V
7
TxD
DataOut
Transmit 422
8
RxD
DataIn
Receive 422
For RS 485 pins 2 and 3 (data +) must be connected, and pins 7 and 8 (data ).
Setting the interface parameters
The interface is parameterised as follows in the delivery condition:
Table 6: RS485 without echo, end point (terminated) standard setting
Function
Status
Echo on
off
Echo off
on
Auto send on
on
Always send on
off
Auto receive on
on
Always receive on
off
Term on
on
Term on
on
CX9020
29
Version 1.1