BECKHOFF CX1100-09xx UPS User Manual
Page 31
Commissioning
Embedded PC
29
Register settings CX1100-09xx
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
0x0D1010
IN-
Register
State_3
State_2
State_1
State_0
reserved
reserved
24V_IN_OK
24V_OUT_OK
+1
charge
state
C7
C6
C5
C4
C3
C2
C1
C0
+2
OUT-
Register
IRQ3
IRQ2
IRQ1
IRQ0
AUTO_RES
DIP_DIS
reserved
Output OFF
+3
DIP-
DATA
D7
D6
D5
D4
D3
D2
D1
D0
+4
identifier
0
"C" (ASCII)
+5
identifier
1
"X" (ASCII)
+6
identifier
2
"11" (DEC)
+7
identifier
3
"90" (DEC)
base address 0D1010
C = charge state 0% = 00h, 100% = FFh
IRQ = binary coded IRQ number; 0000 = disabled
DIP_DIS = 1 : disable DIP switch with DIP-DATA
AUTO_RES = 1 : auto reboot (shutdown after short power failure)
Warning
The AUTO_RES bit must be reset before system shutdown to "0" !
Meaning of STATE-Nibble:
Value
State
0
no function
1
charging
2
full charged
3
discharged
4
discharging and restart
5
output off
6
overload
7
not used
8
not used
9
not used