Installation Instructions


Installation of the PC in the control cabinet

The C3620 and C3640 Industrial PCs are designed for rack mounting in
machine and plant engineering applications.

The ambient conditions specified for operation must be observed (see the
section

Technical data

).

Preparation of the control
cabinet wall

The control cabinet wall must be prepared with the required mounting
opening for the computer unit and the eight holes for the set screws
according to the PC's dimensions (see chapter

Assembly dimensions

).

i

Note

When the unit is installed in an enclosure, adequate space for
ventilation and for opening the PC must be provided.

Please note the following points during installation of the PC:

• Position the PC in such a way that reflections on the screen are

avoided as far as possible.

• Use the position of the screen as a guide for the correct installation

height; it should be optimally visible for the user at all times.

• The PC should not be exposed to direct sunlight.

• When the unit is in its mounting position, the ventilation openings must

not be obstructed.

Warning

Extreme environmental conditions should be avoided as far as
possible. Protect the rear of your PC from dust, humidity and heat.

The clearance above and below the housing must be at least 100 mm
in order to ensure adequate ventilation of the PC.

The ventilation slots of the PC must not be covered.

Installation in a control
cabinet wall

Proceed as follows:

1. Insert the PC at the intended control cabinet wall position and protect it

from falling out, prior to final mounting.

2. Using 8 M4 nuts, fix the PC to the control cabinet wall by screwing the

nuts from the rear onto the set screws of the PC housing.

Earthing measures

Earthing measures

Earthing connections dissipate interference from external power supply
cables, signal cables or cables to peripheral equipment.

Establish a low-impedance connection from the earthing point on the PC
housing to the central earthing point on the control cabinet wall, in which
the computer is being installed. The earthing connection of the Industrial
PC is located beside the power supply connector.

C3620, C3640

11